Bl-1003, Bl-1004, Bl-1006 – Dell POWEREDGE M1000E User Manual
Page 136

60
Fabric OS Message Reference
53-1001767-01
BL-1003
7
Severity
CRITICAL
BL-1003
Message
Faulting blade in slot
.
Probable Cause
Indicates a faulty blade in the specified slot number.
Recommended
Action
Make sure that the blade is seated correctly. If the blade is seated correctly, restart or power cycle
the blade.
Run the systemVerification command to verify that blade does not have hardware problems. To run
this command root access is required. Run the diagPost command to ensure that Power-On
Self-Test (POST) is enabled. Refer to the Fabric OS Command Reference for more information on
these commands.
If the message persists, replace the blade.
Severity
CRITICAL
BL-1004
Message
Suppressing blade fault in slot
.
Probable Cause
Indicates that the specified blade experienced a failure but was not faulted due to a user setting.
Recommended
Action
Restart or power cycle the blade, using the slotPowerOff and slotPowerOn commands.
Run the systemVerification command to verify that the blade does not have hardware problems. To
run this command root access is required. Run the diagPost command to ensure that Power-On
Self-Test (POST) is enabled. Refer to the Fabric OS Command Reference for more information on
these commands.
If the message persists, replace the blade.
Severity
CRITICAL
BL-1006
Message
number> NOT faulted. Peer blade Probable Cause Indicates that the errors (mostly synchronization errors) on this blade are harmless. Probably, the Recommended Action Use the haShow command to verify that the standby CP is healthy. If problem persists remove and Severity INFO
standby control processor (CP) blade connected to the active CP blade has experienced transitory
problems.
reinstall the faulty blade.