HIL-1305

45

Severity

ERROR

HIL-1305

Message

, [HIL-1305], ,, ERROR, , One or two

fans failed. Replace failed fan FRUs immediately.

Probable Cause

Indicates that multiple fan field-replaceable units (FRUs) have failed. This message is often
preceded by a low fan speed message.

Recommended

Action

Replace the faulty fan FRUs immediately.

Severity

ERROR

HIL-1306

Message

, [HIL-1306], ,, ERROR, , Three fans

failed. Replace failed fan FRUs immediately.

Probable Cause

Indicates that three fan field-replaceable units (FRUs) have failed. This message is often preceded
by a low fan speed message.

Recommended

Action

Replace the faulty fan FRUs immediately.

Severity

ERROR

HIL-1307

Message

, [HIL-1307], ,, ERROR, , Four or five

fans failed. Replace failed fan FRUs immediately.

Probable Cause

Indicates that multiple fan field-replaceable units (FRUs) have failed. This message is often
preceded by a low fan speed message.

Recommended

Action

Replace the faulty fan FRUs immediately.

Severity

ERROR

HIL-1308

Message

, [HIL-1308], ,, ERROR, , All fans

failed. Replace failed fan FRUs immediately.

Probable Cause

Indicates that all fans have failed. This message is often preceded by a low fan speed message.