Fabric OS Message Reference

53-1001767-01

FCR-1056

34

Severity

INFO

FCR-1056

Message

, [FCR-1056], ,, INFO, , Switch

WWN> with front domain ID does not support backbone to edge imports.

Probable Cause

Indicates that a switch that does not support backbone-to-edge routing is running in the MetaSAN.

Recommended

Action

No action is required if backbone-to-edge routing is not needed. Otherwise replace the switch with
one that supports backbone to edge routing.

Severity

INFO

FCR-1057

Message

, [FCR-1057], ,, ERROR, , EX_Port(

number>

) incompatible long distance parameters on link.

Probable Cause

Indicates that the port, which is configured in long distance mode, has incompatible long distance
parameters.

Recommended

Action

Check the port configuration on both sides of the link using the portCfgShow command.

Investigate the other switch for more details. Run the errShow command on the other switch to
view the error log for additional messages.

Severity

ERROR

FCR-1058

Message

, [FCR-1058], ,, WARNING, , Port

number> isolated due to mismatched configuration parameter;

reason>.

Probable Cause

Indicates that the specified port was isolated after segmentation caused by mismatched
configuration parameters or by domain ID assigned by the principal switch that did not match the
insistent domain ID of this port.

Recommended

Action

Check the switches on both ends of the link for a possible mismatch in switch or port configuration
parameters such as Operating Mode, E_D_TOV, R_A_TOV, Domain ID Offset, etc.

Run the portCfgExport command to modify the appropriate parameters on the local switch.

Run the appropriate configuration command to modify the switch or port parameters on the remote
switch.

Severity

WARNING