Fabric OS Message Reference
347
53-1001767-01
FW-1446
42
Recommended
Action
No action required, unless there are fewer than 4 power supplies active in the chassis. If there are
fewer than 4, insert additional power supplies so that there are 4 active.
Severity
INFO
FW-1446
Message
supplies now required for 2X redundancy, not enforced by Fabric Watch due to
Switch Status Policy overridden by User.
Probable Cause
Indicates that the switch now requires 4 power supplies for full (2X) redundancy, but the user has
previously overridden the Switch Status Policy values pertaining to number of power supplies. So
those values will not be automatically changed. The default values with no AP blades are: 3 out of
service indicates switch status is DOWN, 0 indicates no checking for switch status MARGINAL. The
default values when an AP blade is or has been present are: 2 out of service indicates switch
status is DOWN, 1 out of service indicates switch status is MARGINAL
Recommended
Action
To maintain full (2X) redundancy and proper monitoring by Fabric Watch, 4 active power supplies
should be supplied and the default values associated with the presence of an AP blade should be
entered with switchStatusPolicyset command.
Severity
WARNING
FW-1447
Message
change contributing factor Core Blade: State>). Probable Cause Indicates that the switch is not in a healthy state. This occurred because the number of core blade Recommended Action Replace the faulty core blade. Severity WARNING FW-1500 Message - Alerts being discarded. Probable Cause Indicates that mail alert overflow condition has occurred. Recommended Action Resolve or disable the mail alert using the fwMailCfg command. Severity WARNING
failures is greater than or equal to the policy set by the switchStatusPolicySet command.