EM-1036
22
Probable Cause
Suggests that since both power supplies associated with one of the two main circuits are present
but faulty, maybe the circuit's switch has been turned off, or the AC power source has been
interrupted for that circuit.
The Switch side value is either "left" or "right" designating which circuit switch, facing the cable side
of the chassis. The Switch side value indicates:
•
left: controls the odd numbered power supply units.
•
right: controls the even numbered power supply units.
Recommended
Action
Check that the identified AC circuit switch is turned on, that the power cord is properly attached
and undamaged, and that the power source is operating properly.
Severity
ERROR
EM-1036
Message
is
not accessible.
Probable Cause
Indicates that the specified field-replaceable unit (FRU) does not seem to be present on the switch.
If the FRU is a world wide name (WWN) card, then default WWN and IP addresses are used for the
switch.
Recommended
Action
Reseat the FRU card.
If the message persists, reboot or power cycle the switch.
Run the systemVerification command to verify that the switch does not have hardware problems. To
run this command root access is required. Refer to the Fabric OS Command Reference for more
information on this command.
If the message persists, replace the FRU.
Severity
WARNING
EM-1037
Message
is no
longer faulted.
Probable Cause
Indicates that the specified power supply has been marked as no longer being faulty, probably
because its AC power supply has been turned on.
Recommended
Action
No action is required.
Severity
INFO