beautypg.com

Table 2-3 – Basler Electric DGC-2020 User Manual

Page 71

background image

Table 2-3. Descriptions for Figure 2-7. Rear Panel for DGC-2020 Hardware Versions 1 and 2

Locator

Description

A, D

The majority of external, DGC-2020 wiring is terminated at 15-position connectors with
compression terminals. These connectors plug into headers on the DGC-2020. The
connectors and headers have a dovetailed edge that ensures proper connector
orientation. Each connector and header is uniquely keyed to ensure that a connector
mates only with the correct header. Connector screw terminals accept a maximum wire
size of 12 AWG (3.31 mm

2

).

B

The mini-B USB socket mates with a standard USB cable and is used with a PC running
BESTCOMSPlus® software for local communication with the DGC-2020.

C

DGC-2020 controllers equipped with an optional, internal, dial-out modem port, connect
to a telephone line through a USOC RJ-11 jack.

E

Connections to the DGC-2020 Start (starter), Run (fuel solenoid), and Pre (glow plug)
output contacts are made directly to each relay through quarter-inch, male, quick-connect
terminals.

F

The DGC-2020 provides a battery backup for the real-time clock. See Section 8,
Maintenance and Troubleshooting, for instructions on replacing the battery. Failure to
replace the battery with Basler Electric P/N 38526 may void the warranty.


9400200990 Rev X

DGC-2020 Human-Machine Interface

2-31

This manual is related to the following products: