Basler Electric DGC-2020 User Manual
Page 501
![background image](https://www.manualsdir.com/files/773941/content/doc501.png)
9400200990 Rev X
DGC-2020 Modbus
™ Communication
B-69
Register
Description
Type
Units
Scaling
Factor
R/W
Range
45556-57
AEM Input Threshold
Pre-Alarm Bits Reg 3
Uint32
N/A
N/A
R
Bit 0 = Not Used
Bit 1 = Not Used
Bit 2 = Thermocouple 2 Under 2
Bit 3 = Thermocouple 2 Under 1
Bit 4 = Thermocouple 2 Over 2
Bit 5 = Thermocouple 2 Over 1
Bit 6 = Thermocouple 2 Out of
Range
Bit 7 = Thermocouple 1 Under 2
Bit 8 = Thermocouple 1 Under 1
Bit 9 = Thermocouple 1 Over 2
Bit 10 = Thermocouple 1 Over 1
Bit 11 = Thermocouple 1 Out of
Range
Bit 12 = RTD Input 8 Under 2
Bit 13 = RTD Input 8 Under 1
Bit 14 = RTD Input 8 Over 2
Bit 15 = RTD Input 8 Over 1
Bit 16 = RTD Input 8 Out of Range
Bit 17 = RTD Input 7 Under 2
Bit 18 = RTD Input 7 Under 1
Bit 19 = RTD Input 7 Over 2
Bit 20 = RTD Input 7 Over 1
Bit 21 = RTD Input 7 Out of Range
Bit 22 = RTD Input 6 Under 2
Bit 23 = RTD Input 6 Under 1
Bit 24 = RTD Input 6 Over 2
Bit 25 = RTD Input 6 Over 1
Bit 26 = RTD Input 6 Out of Range
Bit 27 = RTD Input 5 Under 2
Bit 28 = RTD Input 5 Under 1
Bit 29= RTD Input 5 Over 2
Bit 30 = RTD Input 5 Over 1
Bit 31 = RTD Input 5 Out of Range