Frequency protection (81o/u), Frequency protection (81o/u) -63, Figure 4-53. phase imbalance -63 – Basler Electric DGC-2020 User Manual

Page 173: Underfrequency (81u), Overfrequency (81o), Alternate frequency scale factor

background image

Figure 4-53. Phase Imbalance

A

Pickup: Adjustable from 5 to 100 Vac in 1 Vac increments.

B

Activation Delay: Adjustable from 0 to 30 s in 0.1 s increments.

C

Alarm Configuration: None, Alarm, Pre-Alarm, or Status Only.

D

Hysteresis: Adjustable from 1 to 5 Vac in 1 Vac increments.

E

Low Line Scale Factor: Adjustable from 0.001 to 3 in increments of 0.001.

F

Pickup (Per Unit): Range varies based on the values of the native unit setting and the associated rated

data parameter.

Frequency Protection (81O/U)

Two sets of frequency protection settings are provided: one for underfrequency (81U) and one for
overfrequency (81O).

Underfrequency (81U)

An underfrequency condition is annunciated when the generator frequency decreases below the 81U
pickup setting

A

for the duration of the 81U activation delay setting

B

. An underfrequency annunciation can

be user-selected to trigger a pre-alarm

C

(warning) or alarm

C

(shutdown). An underfrequency annunciation

can also be user-configured to close a programmable output.

A voltage-based inhibit setting

D

prevents an 81U trip from occurring during an underfrequency condition

associated with system startup.

The hysteresis setting

E

functions as an underfrequency dropout by preventing rapid switching of the

pickup output.

Overfrequency (81O)

When the generator frequency increases above the 81O pickup setting

F

for the duration of the 81O

activation delay setting

G

, an overfrequency condition is annunciated. An overfrequency annunciation can

be user-selected to trigger a pre-alarm

H

(warning) or alarm

H

(shutdown). An overfrequency condition can

also be user configured to close a programmable output.

The hysteresis setting

I

functions as an overfrequency dropout by preventing rapid switching of the pickup

output.

The element is disabled when Alarm Configuration is set to “None”. Element status is available in
BESTlogicPlus Programmable Logic when “Status Only” is selected.

Alternate Frequency Scale Factor

An alternate frequency scale factor setting

J

is used for automatic adjustment of the frequency pickup

settings in applications that might utilize more than one operating frequency. For example, a machine that
is configurable between 50 or 60 Hz operation. The scale factor setting is implemented when the DGC-
2020 senses a contact closure at a contact input that is connected to the Alternate Frequency Override
logic element in BESTlogicPlus Programmable Logic. When the Alternate Frequency Override is true, the
scale factor setting serves as a multiplier for the pickup settings. For example, if a scale factor contact
input is received by the DGC-2020 and the scale factor setting is 2.000, the pickup setting will be doubled
(2.000 x PU).

9400200990 Rev X

DGC-2020 BESTCOMSPlus

® Software

4-63