Bus condition detection – Basler Electric DGC-2020 User Manual
Page 445

9400200990 Rev X
DGC-2020 Modbus
™ Communication
B-13
Bus Condition Detection
Register
Description
Type
Units
Scaling
Factor
R/W
Range
42750
Gen Sensing Dead Bus Pickup
Int32
Volt
N/A
RW
0 - 4800
42752
Gen Sensing Dead Bus Time Delay
Int32
Decisecond
Deci
RW
1 - 6000
42754
RESERVED
42756
Gen Sensing Stable Undervoltage Pickup
Int32
Volt
N/A
RW
10 - 99999
42758
Gen Sensing Stable Undervoltage Dropout
Int32
Volt
N/A
RW
10 - 99999
42760
Gen Sensing Stable Overvoltage
Int32
Volt
N/A
RW
10 - 99999
42762
Gen Sensing Stable Overvoltage Dropout
Int32
Volt
N/A
RW
10 - 99999
42764
Gen Sensing Stable Underfrequency Pickup
Int32
CentiHertz
Centi
RW
4600 - 6400
42766
Gen Sensing Stable Underfrequency Dropout
Int32
CentiHertz
Centi
RW
4600 - 6400
42768
Gen Sensing Stable Overfrequency Pickup
Int32
CentiHertz
Centi
RW
4600 - 6400
42770
Gen Sensing Stable Overfrequency Dropout
Int32
CentiHertz
Centi
RW
4600 - 6400
42772
Gen Sensing Fail Time Delay
Int32
Decisecond
Deci
RW
1 - 6000
42774
Gen Sensing Stable Time Delay
Int32
Decisecond
Deci
RW
1 - 6000
42776
RESERVED
42778
Bus Sensing Dead Bus Pickup
Int32
Volt
N/A
RW
0 - 4800
42780
Bus Sensing Dead Bus Time Delay
Int32
Decisecond
Deci
RW
1 - 6000
42782
RESERVED
42784
Bus Sensing Stable Undervoltage Pickup
Int32
Volt
N/A
RW
10 - 9999
42786
Bus Sensing Stable Undervoltage Dropout
Int32
Volt
N/A
RW
10 - 9999
42788
Bus Sensing Stable Overvoltage Pickup
Int32
Volt
N/A
RW
10 - 9999
42790
Bus Sensing Stable Overvoltage Dropout
Int32
Volt
N/A
RW
10 - 9999
42792
Bus Sensing Stable Underfrequency Pickup
Int32
CentiHertz
Centi
RW
4600 - 6400
42794
Bus Sensing Stable Underfrequency Dropout
Int32
CentiHertz
Centi
RW
4600 - 6400
42796
Bus Sensing Stable Overfrequency Pickup
Int32
CentiHertz
Centi
RW
4600 - 6400
42798
Bus Sensing Stable Overfrequency Dropout
Int32
CentiHertz
Centi
RW
4600 - 6400
42800
Bus Sensing Fail Time Delay
Int32
Decisecond
Deci
RW
1 - 6000
42802
Bus Sensing Stable Time Delay
Int32
Decisecond
Deci
RW
1 - 6000
42804
RESERVED
42806
Gen Dead Status
Int32
N/A
N/A
R
0 - 1
42808
Gen Stable Status
Int32
N/A
N/A
R
0 - 1
42810
Gen Fail Status
Int32
N/A
N/A
R
0 - 1
42812
Bus Dead Status
Int32
N/A
N/A
R
0 - 1
42814
Bus Stable Status
Int32
N/A
N/A
R
0 - 1
42816
Bus Fail Status
Int32
N/A
N/A
R
0 - 1
42818
Gen Stable Low Line Scale Factor
Float
N/A
N/A
RW
0.001 - 3
42820
Bus Stable Low Line Scale Factor
Float
N/A
N/A
RW
0.001 - 3
42822
Gen Stable Alternate Frequency Scale Factor
Float
N/A
N/A
RW
0.001 - 100
42824
Bus Stable Alternate Frequency Scale Factor
Float
N/A
N/A
RW
0.001 - 100
42826-
3250
FUTURE USE
43252
User Configurable Input 1 Config Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-
alarm
43254
User Configurable Input 1 Time Delay
Int32
Second
N/A
RW
0 - 300
43258
RESERVED
43260
User Configurable Input 2 Config Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-
alarm
43262
User Configurable Input 2 Time Delay
Int32
Second
N/A
RW
0 - 300
43266
RESERVED
43268
User Configurable Input 3 Config Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-
alarm
43270
User Configurable Input 3 Time Delay
Int32
Second
N/A
RW
0 - 300
43272-74
RESERVED