Mdec pre-alarms, Mtu status – Basler Electric DGC-2020 User Manual
Page 484
B-52
DGC-2020 Modbus
™ Communication
9400200990 Rev X
Register
Description
Type
Units
Scaling
Factor
R/W
Range
44982-83
MDEC Pre-Alarms
Int32
N/A
N/A
R
Bit 0 = Not Used
Bit 1 = Not Used
Bit 2 = Not Used
Bit 3 = Not Used
Bit 4 = Not Used
Bit 5 = Not Used
Bit 6 = Not Used
Bit 7 = Not Used
Bit 8 = Not Used
Bit 9 = Not Used
Bit 10 = Not Used
Bit 11 = Not Used
Bit 12 = Not Used
Bit 13 = Not Used
Bit 14 = Not Used
Bit 15 = Not Used
Bit 16 = Not Used
Bit 17 = Not Used
Bit 18 = Not Used
Bit 19 = Not Used
Bit 20 = Not Used
Bit 21 = Not Used
Bit 22 = Not Used
Bit 23 = Not Used
Bit 24 = High Fuel Filter Diff
Pressure
Bit 25 = Overspeed Test On
Bit 26 = Ambient Temp
Bit 27 = High Temp Coil 3
Bit 28 = High Temp Coil 2
Bit 29 = High Temp Coil 1
Bit 30 = High Pressure Input 2
Bit 31 = High Pressure Input 1
44984-85
MTU Status
Int32
N/A
N/A
R
Bit 0 = Not Used
Bit 1 = Not Used
Bit 2 = Not Used
Bit 3 = Not Used
Bit 4 = Not Used
Bit 5 = Not Used
Bit 6 = Not Used
Bit 7 = Not Used
Bit 8 = Not Used
Bit 9 = Not Used
Bit 10 = Not Used
Bit 11 = Not Used
Bit 12 = Not Used
Bit 13 = Not Used
Bit 14 = Not Used
Bit 15 = Not Used
Bit 16 = Not Used
Bit 17 = Not Used
Bit 18 = Not Used
Bit 19 = Not Used
Bit 20 = ECU Shutdown
Bit 21 = Priming Pump ON
Bit 22 = CAN Mode Feedback
Bit 23 = Preheat Temp Not
Reached
Bit 24 = Load Gen On
Bit 25 = Cylinder Cutout
Bit 26 = Engine Running
Bit 27 = Speed Decrease
Bit 28 = Speed Increase
Bit 29 = Speed Demand Fail Mode
Bit 30 = External Stop Active
Bit 31 = ECU Override