Basler Electric DGC-2020 User Manual
Page 592

Fault
Code
Number
String
Description
65
LO P FUEL
Fuel supply pressure too low (limit 1).
66
SS P FUEL
Fuel supply pressure too low (limit 2).
67
HI T COOLANT
Coolant temperature too high (limit 1).
68
SS T COOLANT
Coolant temperature too high (limit 2).
69
L1 T EXTERN 1
Limit 1, out of range.
70
L2 T EXTERN 1
Limit 2, out of range.
71
L1 T EXTERN 2
Limit 1, out of range.
72
L2 T EXTERN 2
Limit 2, out of range.
73
L1 P EXTERN 1
Limit 1, out of range.
74
L2 P EXTERN 1
Limit 2, out of range.
75
L1 P EXTERN 2
Limit 1, out of range.
76
L2 P EXTERN 2
Limit 2, out of range.
77
LIM EXT CLNT LEV
Binary signal 1 Plant active.
78
LIM INTERCLR LEV
Binary signal 2 Plant active.
79
L BIN EXTERN 3
Binary signal 3 Plant active.
80
L BIN EXTERN 4
Binary signal 4 Plant active.
81
AL RAIL LEAKAGE
Rail pressure gradient too low for Start or too high for Stop.
82
HI P FUEL COMON RAIL
Rail pressure > setpoint value.
83
LO P FUEL COMMON RAIL
Rail pressure < setpoint value.
85
HI T UMBLASSEN
‘Umblasen’ temperature too high (limit 1).
86
SS T UMBLASSEN
‘Umblasen’ temperature too high (limit 2).
89
SS SPEED TOO LOW
Engine is being stalled. The engine speed of the normally operating engine
dropped below the limit from parameter 2.2500.027 Limit Engine Speed Low
without any stop request. For safety reason the engine is stopped when this
event occurs.
90
SS IDLE SPEED LOW
Idle speed not reached.
91
SS RELEASE SPEED LO
Acceleration speed not reached.
92
SS STARTER SPEED LO
Starter speed not reached.
93
SS PREHT TMP
Preheat temperature too low (limit 2).
94
LO PREHT TMP
Preheat temperature too low (limit 1).
95
AL PRELUBE FAULT
Prelubrication fault.
99
DUMMY FAULT
Dummy fault - this is not a real fault, but is used on some ECU’s to test the fault
reporting mechanism.
100
EDM NOT VALID
Checksum fault EDM.
101
IDM NOT VALID
Checksum fault IDM.
102
INVLD FUEL CNS 1
Fuel consumption counter detect.
103
INVLD FUEL CNS 2
Consumption monitoring 2 not valid.
104
ENG HRS INVALID 1
Engine Hours Counter defect.
105
ENG HRS INVALID 2
Checksum fault.
106
ERR REC1 INVALID
Checksum fault.
107
ERR REC2 INVALID
Checksum fault.
118
LO ECU SUPPLY VOLTS
Power supply voltage too low (limit 1).
119
LOLO ECU SUPPLY VOLTS
Power supply voltage too low (limit 2).
120
HI ECU SUPPLY VOLTS
Power supply voltage too high (limit 1).
121
HIHI ECU SUPPLY VOLTS
Power supply voltage too high (limit 2).
122
HI T ECU
Temperature of electronic too high (limit 1).
134
15v POSECU DEFCT
Internal electronic fault.
136
15V NEGECU DEFCT
Internal electronic fault.
137
L1 5V BUFFR TEST
Pressure-sensor fault, pressure-sensor wiring, or internal electronic fault.
138
SENSOR PWR DEFCT
Pressure-sensor fault, pressure-sensor wiring, or internal electronic fault.
D-2
DGC-2020 MTU Fault Codes
9400200990 Rev X