beautypg.com

Basler Electric DGC-2020 User Manual

Page 547

background image

9400200990 Rev X

DGC-2020 Modbus

™ Communication

B-115

Register

Description

Type

Units

Scaling

Factor

R/W

Range

46926

Battery Charge Failed
Contact Input

Int32

N/A

N/A

RW

-1 = None
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
4 = Input 5
5 = Input 6
6 = Input 7
7 = Input 8
8 = Input 9
9 = Input 10
10 = Input 11
11 = Input 12
12 = Input 13
13 = Input 14
14 = Input 15
15 = Input 16

46928

Battery Charge Failed
Config Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm

46930

Battery Charge Failed
Time Delay

Int32

Second

N/A

RW

0 – 300

46932

Battery Charge Failed
Engine Running Only

Int32

N/A

N/A

RW

0 = Always
1 = While Engine Running Only

46934

Fuel Leak Detect
Contact Input

Int32

N/A

N/A

RW

-1 = None
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
4 = Input 5
5 = Input 6
6 = Input 7
7 = Input 8
8 = Input 9
9 = Input 10
10 = Input 11
11 = Input 12
12 = Input 13
13 = Input 14
14 = Input 15
15 = Input 16

46936

Fuel Leak Detect Config
Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm

46938

Fuel Leak Detect Time
Delay

Int32

Second

N/A

RW

0 – 300

46940

Fuel Leak Detect
Engine Running Only

Int32

N/A

N/A

RW

0 = Always
1 = While Engine Running Only

46942

Single Phase
Connection Override
Contact Input

Int32

N/A

N/A

RW

-1 = None
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
4 = Input 5
5 = Input 6
6 = Input 7
7 = Input 8
8 = Input 9
9 = Input 10
10 = Input 11
11 = Input 12
12 = Input 13
13 = Input 14
14 = Input 15
15 = Input 16

This manual is related to the following products: