Basler Electric DGC-2020 User Manual
Page 547
9400200990 Rev X
DGC-2020 Modbus
™ Communication
B-115
Register
Description
Type
Units
Scaling
Factor
R/W
Range
46926
Battery Charge Failed
Contact Input
Int32
N/A
N/A
RW
-1 = None
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
4 = Input 5
5 = Input 6
6 = Input 7
7 = Input 8
8 = Input 9
9 = Input 10
10 = Input 11
11 = Input 12
12 = Input 13
13 = Input 14
14 = Input 15
15 = Input 16
46928
Battery Charge Failed
Config Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
46930
Battery Charge Failed
Time Delay
Int32
Second
N/A
RW
0 – 300
46932
Battery Charge Failed
Engine Running Only
Int32
N/A
N/A
RW
0 = Always
1 = While Engine Running Only
46934
Fuel Leak Detect
Contact Input
Int32
N/A
N/A
RW
-1 = None
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
4 = Input 5
5 = Input 6
6 = Input 7
7 = Input 8
8 = Input 9
9 = Input 10
10 = Input 11
11 = Input 12
12 = Input 13
13 = Input 14
14 = Input 15
15 = Input 16
46936
Fuel Leak Detect Config
Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
46938
Fuel Leak Detect Time
Delay
Int32
Second
N/A
RW
0 – 300
46940
Fuel Leak Detect
Engine Running Only
Int32
N/A
N/A
RW
0 = Always
1 = While Engine Running Only
46942
Single Phase
Connection Override
Contact Input
Int32
N/A
N/A
RW
-1 = None
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
4 = Input 5
5 = Input 6
6 = Input 7
7 = Input 8
8 = Input 9
9 = Input 10
10 = Input 11
11 = Input 12
12 = Input 13
13 = Input 14
14 = Input 15
15 = Input 16