Pulse outputs – Basler Electric DGC-2020 User Manual
Page 444

B-12
DGC-2020 Modbus
™ Communication
9400200990 Rev X
Register
Description
Type
Units
Scaling
Factor
R/W
Range
42410
kvar Setpoint
Float
Percent
N/A
RW
(-100) - 100
42412
PF Setpoint
Int32
N/A
Centi
RW
160 - 240
42414
var Control Mode
Int32
N/A
N/A
RW
0 = var Control
1 = PF Control
42416
Load Share Interface
Int32
N/A
N/A
RW
0 = Analog Load Share
Line
1 = Ethernet Comms
42418
Remote Speed Bias Source
Int32
N/A
N/A
RW
0 = User Setting
1 = LSM Analog Input
1
2 = AEM Analog Input
1
3 = AEM Analog Input
2
4 = AEM Analog Input
3
5 = AEM Analog Input
4
6 = AEM Analog Input
5
7 = AEM Analog Input
6
8 = AEM Analog Input
7
9 = AEM Analog Input
8
42420
RESERVED
42422
RESERVED
42424
LSM Aux Input Source
Int32
N/A
N/A
RW
0 = LSM Local Aux
Input
1 = LSM System
Manager
42426
kW Ramp Status
Int32
N/A
N/A
R
0 = none
1 = up
2 = down
42428
kvar Ramp Status
Int32
N/A
N/A
R
0 = none
1 = up
2 = down
42430
Speed Trim Bias Range Percent x 100
Data
Int32
CentiPercent
Centi
RW
0 - 500
42432
kW Ramp Overshoot Reduction
Percent Data
Int32
Percent
N/A
RW
0 - 100
42434
kvar Ramp Overshoot Reduction
Percent Data
Int32
Percent
N/A
RW
0 - 100
42436
Speed Trim Deadband
Uint32
CentiHertz
Centi
RW
0 - 100
42438
Volt Trim Deadband
Uint32
DeciPercent
Deci
RW
0 - 20
42440
kW Parallel To Mains Gain
Float
N/A
N/A
RW
0 - 1000
42442
kvar Parallel To Mains Gain
Float
N/A
N/A
RW
0 - 1000
42444-
498
FUTURE USE
Pulse Outputs
Register
Description
Type
Units
Scaling Factor
R/W
Range
42500
AVR Correction Pulse Width
Int32
Decisecond
Deci
RW
0 - 999
42502
AVR Correction Pulse Interval
Int32
Decisecond
Deci
RW
0 - 999
42504
AVR Bias Contact Type
Int32
N/A
N/A
RW
0 = Continuous
1 = Proportional
42506
RESERVED
42508
Governor Correction Pulse Width
Int32
Decisecond
Deci
RW
0 - 999
42510
Governor Correction Pulse Interval
Int32
Decisecond
Deci
RW
0 - 999
42512
Governor Bias Contact Type
Int32
Decisecond
Deci
RW
0 = Continuous
1 = Proportional
42514
RESERVED
42516-748
FUTURE USE