Communication interface, Type tests, Environment – Basler Electric DGC-2020 User Manual
Page 388: Ul approval (cem-2020 only), Ul approval (cem-2020h only), Csa certification, Nfpa compliance, Ce compliance, Communication interface -2, Can bus -2
Communication Interface
CAN Bus
Differential Bus Voltage ............. 1.5 to 3 Vdc
Maximum Voltage ......................
–32 to +32 Vdc with respect to negative battery terminal
Communication Rate ................. 250 kb/s
Type Tests
Shock
Withstands 15 G in 3 perpendicular planes.
Vibration
Swept over the following ranges for 12 sweeps in each of three mutually perpendicular planes with each
15-minute sweep consisting of the following:
5 to 29 to 5 Hz ........................... 1.5 G peak for 5 min.
29 to 52 to 29 Hz ....................... 0.036” Double Amplitude for 2.5 min.
52 to 500 to 52 Hz ..................... 5 G peak for 7.5 min.
Ignition System
Tested in closed proximity to an unshielded, unsuppressed Altronic DISN 800 ignition system.
HALT (Highly Accelerated Life Testing)
HALT is used by Basler Electric to prove that our products will provide the user with many years of
reliable service. HALT subjects the device to extremes in temperature, shock, and vibration to simulate
years of operation, but in a much shorter period span. HALT allows Basler Electric to evaluate all possible
design elements that will add to the life of this device. As an example of some of the extreme testing
conditions, the CEM-2020 was subjected to temperature tests (tested over a temperature range of
–80°C
to +130
°C),
vibration tests (of 5 to 50 G at +25
°C), and temperature/vibration tests (tested at 10 to 20 G
over a temperature range of
–60°C to +100°C). Combined temperature and vibration testing at these
extremes proves that the CEM-2020 is expected to provide long-term operation in a rugged environment.
Note that the vibration and temperature extremes listed in this paragraph are specific to HALT and do not
reflect recommended operation levels. These operational ratings are included in this section.
Environment
Temperature
Operating.............................
–40 to +70°C (–40 to +158°F)
Storage ................................
–40 to +85°C (–40 to +185°F)
Humidity ..................................... IEC 68-2-38
UL Approval (CEM-2020 Only)
“cURus” recognized to UL Standard 508 & CSA Standard C22.2 No. 14.
UL Approval (CEM-2020H Only)
UL recognized to UL Standard 508.
CSA Certification
CSA certified to Standard C22.2 No.14.
NFPA Compliance
Complies with NFPA Standard 110, Standard for Emergency and Standby Power.
CE Compliance
This product complies with the requirements of the following EC Directives:
•
Low Voltage Directive (LVD) - 73/23/EEC as amended by 93/68/EEC
•
Electromagnetic Compatibility (EMC) - 89/336/EEC as amended by 92/31/EEC and 93/68/EEC
10-2
DGC-2020 CEM-2020 (Contact Expansion Module)
9400200990 Rev X