Interdependence of preset multiple register data, Current parameter table, Breaker management – Basler Electric DGC-2020 User Manual
Page 440
B-8
DGC-2020 Modbus
™ Communication
9400200990 Rev X
Interdependence of Preset Multiple Register Data
Preset Multiple Register data is collectively written only after the query has been determined to be legal,
which includes a range-check of the entire data block. Therefore, data which must be written prior to other
data must use a separate query. For example, a Preset Multiple Register Query of the entire Contiguous
Write Block (40023-40055) to set the Battery Overvoltage Pre-alarm Threshold atop the 24V range and
change the Battery Volts from 12V to 24V will fail. The change to 24V would occur simultaneously to
setting the Pre-alarm Threshold, and the threshold value range-check will use the current 12V range.
Mapping - DGC-2020 Parameters into Modicon Address Space
Current Parameter Table
The DGC-2020 maps all non-legacy parameters into the Holding Register address space (42000 and
above). Query address N will access the Holding Register N+1.
Breaker Management
Register
Description
Type
Units
Scaling
Factor
R/W
Range
42000
Gen Breaker Configured
Int32
N/A
N/A
RW
0 = Not
Configured
1 = Configured
42002
Gen Breaker Open Pulse Time
Int32
Centisecond
Centi
RW
1 - 80
42004
Gen Breaker Close Pulse Time
Int32
Centisecond
Centi
RW
1 - 80
42006
Gen Breaker Contact Type
Int32
N/A
N/A
RW
0 = Pulse
1 = Continuous
42008
Gen Breaker Close Time
Int32
Millisecond
N/A
RW
0 - 800
42010
RESERVED
42012
Mains Breaker Configured
Int32
N/A
N/A
RW
0 = Not
Configured
1 = Configured
42014
Mains Breaker Open Pulse Time
Int32
Centisecond
Centi
RW
1 - 80
42016
Mains Breaker Close Pulse Time
Int32
Centisecond
Centi
RW
1 - 80
42018
Mains Breaker Output Continuous
Int32
N/A
N/A
RW
0 = Pulse
1 = Continuous
42020
Mains Breaker Close Time
Int32
Millisecond
N/A
RW
0 - 800
42022
RESERVED
42024
Synchronizer Type
Int32
N/A
N/A
RW
1 = Anticipatory
2 = Phase Lock
Loop
42026
RESERVED
42028
Slip Frequency
Int32
CentiHertz
Centi
RW
1 - 50
42030
Breaker Closing Angle
Int32
DeciDegree
Deci
RW
30 - 200
42032
Regulation Offset
Int32
DeciPercent
Deci
RW
20 - 150
42034
Vgen > Vbus
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
42036
Fgen > Fbus
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
42038-40
RESERVED
42042
Breaker Close Wait Time
Float
Second
N/A
RW
0.1 - 600
42044
Sync Time Delay
Float
Second
N/A
RW
0.1 - 0.8
42046
Sync Fail Time Delay
Float
Second
N/A
RW
0.1 - 600
42048
Mains Fail Transfer Enable
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
42050
Gen Breaker Status
Int32
N/A
N/A
R
0 = Open
1 = Closed
42052
Mains Breaker Status
Int32
N/A
N/A
R
0 = Open
1 = Closed
42054
Mains Fail Transfer Delay
Int32
Second
N/A
RW
0 - 300
42056
Mains Fail Return Delay
Int32
Second
N/A
RW
0 - 1800
42058
Mains Fail Max Transfer Time
Int32
Second
N/A
RW
1 - 120
42060
RESERVED
42062
Dead Bus Close Enable
Int32
N/A
N/A
RW
0 = Disable
1 = Enable