DGC-2020 Modbus
™ Communication
9400200990 Rev X
Register
Description
Type
Units
Scaling
Factor
R/W
Range
44066-67
Modem Dialout Conditions 4
Uint32
N/A
N/A
RW
Bit 0 = Not Used
Bit 1 = Not Used
Bit 2 = Not Used
Bit 3 = Not Used
Bit 4 = Not Used
Bit 5 = Not Used
Bit 6 = Not Used
Bit 7 = Not Used
Bit 8 = Not Used
Bit 9 = Not Used
Bit 10 = Not Used
Bit 11 = Not Used
Bit 12 = Not Used
Bit 13 = Not Used
Bit 14 = Not Used
Bit 15 = Common Pre-Alarm
Bit 16 = Common Alarm
Bit 17 = Unexpected Shutdown Alarm
Bit 18 = ECU Shutdown
Bit 19 = DEF Inducement Override Pre-
Alarm
Bit 20 = DEF Severe Inducement Pre-
Alarm
Bit 21 = DEF Pre-Severe Inducement
Pre-Alarm
Bit 22 = DEF Engine Derate Pre-Alarm
Bit 23 = DEF Fluid Empty Pre-Alarm
Bit 24 = DEF Fluid Low Pre-Alarm
Bit 25 = DPF Soot Level Severely High
Pre-Alarm
Bit 26 = DPF Soot Level Moderately
High Pre-Alarm
Bit 27 = DPF Soot Level High Pre-Alarm
Bit 28 = High Exhaust Temp Pre-Alarm
Bit 29 = DPF Regeneration Inhibited
Pre-Alarm
Bit 30 = DPF Regeneration Required
Pre-Alarm
Bit 31 = 81 ROCOF DF/DT Trip
44068
Active IP Address
Uint32
N/A
N/A
R
0 - 4294967295
44070
Gateway IP Address
Uint32
N/A
N/A
R
0 - 4294967295
44072
Subnet Mask
Uint32
N/A
N/A
R
0 - 4294967295
44074-248
FUTURE USE
Protection
Register
Description
Type
Units
Scaling
Factor
R/W
Range
44250
3 Phase Overcurrent Pickup
(51-1)
Uint32
CentiAmp
Centi
RW
18 - 775
44252
3 Phase Overcurrent Time Dial
(51-1)
Uint32
DeciUnit
Deci
RW
0 - 72000
44254
3 Phase Overcurrent Curve
(51-1)
Uint32
N/A
N/A
RW
0 = S1 Curve
1 = S2 Curve
2 = L1 Curve
3 = L2 Curve
4 = D Curve
5 = M Curve
6 = I1 Curve
7 = I2 Curve
8 = V1 Curve
9 = V2 Curve
10 = E1 Curve
11 = E2 Curve
12 = A Curve
13 = B Curve
14 = C Curve
15 = G Curve
16 = F Curve
17 = Programmable