Figure 4-46. Scale Factors

A

Alternate Frequency Scale Factor: Adjustable from 0.001 to 100 in increments of 0.001.

B

Voltage Low Line Scale Factor: Adjustable from 0.001 to 100 in increments of 0.001.

C

Current Low Line Scale Factor: Adjustable from 0.001 to 100 in increments of 0.001.

Alarm Configuration

DGC-2020 alarms and pre-alarms can be used to annunciate system, genset, and engine sender
conditions. The description of the alarm configuration settings is organized as follows:

Horn Configuration

Pre-Alarms

Alarms

Sender Fail

Horn Configuration

Horn

An output contact configured (through programmable logic) to energize a horn

A

can be enabled and

disabled through BESTCOMSPlus or at the DGC-2020 front panel.

Not In Auto Horn Enable

This setting

B

allows the horn to annunciate when the DGC-2020 is not in auto mode.

The BESTCOMSPlus Horn Configuration screen is illustrated in Figure 4-47.

Figure 4-47. Horn Configuration

A

Horn: Enable or Disable.

B

Not In Auto Horn Enable: Enable or Disable.

Pre-Alarms

A pre-alarm is annunciated when a condition programmed to trigger a pre-alarm is met. When a pre-alarm
condition exists, it is annunciated (flashed) on the LCD, the front panel Alarm indicator flashes on and off
and the Horn output (if programmed and enabled) alternates between an energized and de-energized
state. The audible alarm is reset by pressing the front panel Alarm Silence pushbutton. When a pre-alarm
condition ceases to exist for most pre-alarms, all displayed annunciations are reset automatically. Certain
pre-alarms do not clear automatically and must be cleared by either pressing the reset button on the front
panel or providing an input to the Reset logic element in BESTlogicPlus. The following pre-alarms do not
clear automatically:

Weak Battery Pre-Alarm

Breaker Close Fail Pre-Alarms

Breaker Open Fail Pre-Alarms

4-52

DGC-2020 BESTCOMSPlus

® Software

9400200990 Rev X