DGC-2020 Modbus
™ Communication
9400200990 Rev X
Holding
Register
Parameter
Range
Read/Write
Supported
Data
Format
Units
40054
Threshold
40-80 (12V)
80-160 (24V)
R W
0.1 VoltDC
40055
Pre-alarm Activation Time Delay
1-10
R W
Seconds
40056-59
RESERVED
HIGH COOLANT TEMP ALARM
40060
Enable
0-1
R W
0 =Off
1 =On
40061
Threshold
100-280
R W
Degrees F
40062
Arming Delay after Crank
Disconnect
60
R W
Seconds
LOW OIL PRESSURE ALARM
40063
Enable
0-1
R W
0 =Off
1 =On
40064
Threshold
3-100
R W
PSI
40065
Arming Delay after Crank
Disconnect
5-15
R W
Seconds
OVERSPEED ALARM
40066
Enable
0-1
R W
0 =Off
1 =On
40067
Threshold
105-140
R W
% of Rated
40068
Alarm Activation Time Delay
0-500
R W
MilliSec
40069-71
RESERVED
CRANKING PARAMETERES
40072
Cranking Style
0-1
R W
0=Contin.
1=Cycle
40073
Number of Crank Cycles
1-7
R W
40074
Cycle Crank Time
5-15
R W
Seconds
40075
Continuous Crank Time
1-60
R W
Seconds
40076
Crank Disconnect Limit
10-100
R W
% of Rated
40077
Pre-crank Delay
0-30
R W
Seconds
SYSTEM MONITOR
40078
Remaining Cooldown Time
0-60
R
Minutes
40079
RESERVED
40080
Active Speed Signal Sources
1-4
R
0 = None
1 = MPU
2 = Gen Freq
4 = CAN Bus
40081
Sender Failure Alarm Code
individual bits
are 0 or 1
R
b0 = High Coolant Temperature
b1 = Oil Pressure
b2 = Fuel Level
b3 = Magnetic Pick-up
b4 = Generator Voltage Sensing
b5 = Battery Charger Fail
b6 = Coolant Level Sender Fail
b7 not used
40082
Alarm Codes
individual bits
are 0 or 1
R
b0=High Coolant Temperature
b1=Low Coolant Level
b2=Low Fuel Level
b3=Emergency Stop
b4=Sender Failure
b5=Over Crank
b6=Over Speed
b7=Low Oil Pressure
Rev. 3.04 Added:
b8 = CAN Fail