Basler Electric DGC-2020 User Manual
Page 569

9400200990 Rev X
DGC-2020 Modbus
™ Communication
B-137
Holding
Register
Parameter
Range
Read/Write
Supported
Data
Format
Units
40052
Remote Delay Time
0-20
R W
0=Min.
1 =10
2 = 20
etc.
20 =200
MilliSec 10
40053
Comm Parity
0-2
R W
0 =None
1 =Odd
2 =Even
40054
Device Address
1-247
R W
40055
Modern Time Delay
0-9999
R W
Microseconds
40056
Embedded Code Version No.
100-9999
R -
Version No. x 100
PARAMETER SETTINGS
40078
Remote (PC) Emergency Stop
0-1
- W
0 =Off
1 = Stop
40079
Remote Start / Stop
0-1
- W
0 =Stop
1 =Start
40080
40081
Settings Source
0-2
R W
0 =Factory
1 =OEM
2 =User
40082
Save Settings
Data=Don’t Care
- W
40083
SYSTEM PARAMETERS
40091
Generator Connection
0-2
R W
0=3ph L-L
1=3ph L-N
2=1ph A-B
40092
NFPA Level
0-2
R W
0 =Off
1 =Level 1
2 =Level 2
40093
Unit System
0-1
R W
0=English
1=Metric
40094
Battery Volts
0-1
R W
0=12 VDC
1=24 VDC
40095
Generator Frequency
0-1
R W
0=50 HZ
1=60 HZ
40096
Rated Engine RPM
750-3600
R W
RPM
40097
Rated Engine RPM Minimum
750
R -
RPM
40098
Rated Engine RPM Maximum
3600
R -
RPM
40099
Rated Engine RPM Stepsize
50
R -
RPM
40100
Number Flywheel Teeth
50-500
R W
40101
Number Flywheel Teeth
Minimum
50
R -
40102
Number Flywheel Teeth
Maximum
500
R -
40103
Number Flywheel Teeth
Stepsize
1
R -
40104
Genset KW Rating
25-9999
R W
KWatt
40105
Genset KW Rating Minimum
25
R -
KWatt
40106
Genset KW Rating Maximum
9999
R -
KWatt
40107
Genset KW Rating Stepsize
1
R -
KWatt
40108
No Load Cool Down Time
0-60
R W
Minutes
40109
No Load Cool Down Time
Minimum
0
R -
Minutes
40110
No Load Cool Down Time
Maximum
60
R -
Minutes
40111
No Load Cool Down Time
Stepsize
5
R -
Minutes
40112
Alternator Frequency Rated
100-900
R W
Hertz
40113
Alternator Frequency Rated
Minimum
100
R -
Hertz