9400200990 Rev X
DGC-2020 Modbus
™ Communication
B-27
Register
Description
Type
Units
Scaling
Factor
R/W
Range
44256
3 Phase Overcurrent Alarm
Configuration (51-1)
Uint32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
44258
1 Phase Overcurrent Pickup
(51-1)
Uint32
CentiAmp
Centi
RW
18 - 775
44260
1 Phase Overcurrent Time Dial
(51-1)
Uint32
DeciUnit
Deci
RW
0 - 72000
44262
1 Phase Overcurrent Curve
(51-1)
Uint32
N/A
N/A
RW
0 = S1 Curve
1 = S2 Curve
2 = L1 Curve
3 = L2 Curve
4 = D Curve
5 = M Curve
6 = I1 Curve
7 = I2 Curve
8 = V1 Curve
9 = V2 Curve
10 = E1 Curve
11 = E2 Curve
12 = A Curve
13 = B Curve
14 = C Curve
15 = G Curve
16 = F Curve
17 = Programmable
44264
1 Phase Overcurrent Alarm
Configuration (51-1)
Uint32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
44266
Phase Imbalance Pickup
Uint32
Volt
N/A
RW
5 - 100
44268
Phase Imbalance Activation
Delay
Uint32
Decisecond
Deci
RW
0 - 300
44270
Phase Imbalance Alarm
Configuration
Uint32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
44272
3 Phase Undervoltage Pickup
(27-1)
Uint32
Volt
N/A
RW
70 - 1000
44274
3 Phase Undervoltage Activation
Delay (27-1)
Uint32
Decisecond
Deci
RW
0 - 300
44276
3 Phase Undervoltage Inhibit
Frequency (27-1)
Uint32
Hertz
N/A
RW
20 - 400
44278
3 Phase Undervoltage Alarm
Configuration (27-1)
Uint32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
44280
1 Phase Undervoltage Pickup
(27-1)
Uint32
Volt
N/A
RW
70 - 1000
44282
1 Phase Undervoltage Activation
Delay (27-1)
Uint32
Decisecond
Deci
RW
0 - 300
44284
1 Phase Undervoltage Inhibit
Frequency (27-1)
Uint32
Hertz
N/A
RW
20 - 400
44286
1 Phase Undervoltage Alarm
Configuration (27-1)
Uint32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
44288
3 Phase Overvoltage Pickup
(59-1)
Uint32
Volt
N/A
RW
70 - 1000
44290
3 Phase Overvoltage Activation
Delay (59-1)
Uint32
Decisecond
Deci
RW
0 - 300
44292
3 Phase Overvoltage Alarm
Configuration (59-1)
Uint32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
44294
1 Phase Overvoltage Pickup
(59-1)
Uint32
Volt
N/A
RW
70 - 1000