Mtu alarm metering, Mtu pre-alarm metering – Basler Electric DGC-2020 User Manual

Page 469

background image

9400200990 Rev X

DGC-2020 Modbus

™ Communication

B-37

Register

Description

Type

Units

Scaling

Factor

R/W

Range

44816-17

MTU Alarm Metering

Int32

N/A

N/A

R

Bit 0 = Not Used
Bit 1 = Not Used
Bit 2 = Not Used
Bit 3 = Not Used
Bit 4 = Not Used
Bit 5 = Not Used
Bit 6 = Not Used
Bit 7 = Not Used
Bit 8 = Not Used
Bit 9 = Not Used
Bit 10 = Not Used
Bit 11 = Not Used
Bit 12 = Not Used
Bit 13 = Not Used
Bit 14 = Not Used
Bit 15 = Not Used
Bit 16 = Not Used
Bit 17 = Not Used
Bit 18 = Not Used
Bit 19 = Not Used
Bit 20 = Not Used
Bit 21 = Not Used
Bit 22 = Not Used
Bit 23 = High ECU Supply
Bit 24 = Combined Red
Bit 25 = Overspeed
Bit 26 = Low Oil Pressure
Bit 27 = Low Fuel Delivery Press.
Bit 28 = Low Aftercooler Coolant
Level
Bit 29 = High Coolant Temp
Bit 30 = High Oil Temp
Bit 31 = High Charge Air Temp

44818-19

MTU Pre-Alarm
Metering

Int32

N/A

N/A

R

Bit 0 = Low Storage Tank
Bit 1 = High Storage Tank
Bit 2 = Low Day Tank
Bit 3 = High Day Tank
Bit 4 = Alternator Winding Temp
Bit 5 = Idle Speed Low
Bit 6 = Run Up Speed Low
Bit 7 = Start Speed Low
Bit 8 = Priming Fault
Bit 9 = Low Charge Air Coolant
Level
Bit 10 = High Fuel Temp.
Bit 11 = High Exhaust Temp. B
Bit 12 = High Exhaust Temp. A
Bit 13 = Low ECU Supply Voltage
Bit 14 = Engine Speed Too Low
Bit 15 = High Voltage Supply
Bit 16 = Low Voltage Supply
Bit 17 = Speed Demand Fail
Bit 18 = ECU Faulty
Bit 19 = Combined Yellow
Bit 20 = Low Oil Press.
Bit 21 = Low Fuel Delivery Press.
Bit 22 = Low Charge Air Press.
Bit 23 = Low Coolant Level
Bit 24 = Low Fuel Rail Press.
Bit 25 = High Fuel Rail Press.
Bit 26 = Shutdown Override
Bit 27 = High Coolant Temp.
Bit 28 = High Charge Air Temp.
Bit 29 = High Intercooler Temp.
Bit 30 = High Oil Temp.
Bit 31 = High ECU Temp.