B-120
DGC-2020 Modbus
™ Communication
9400200990 Rev X
Register
Description
Type
Units
Scaling
Factor
R/W
Range
47140
AEM1 RTD6 Over2
Threshold
Int32
Deg F
N/A
RW
-58 - 482
47142
AEM1 RTD6 Under1
Threshold
Int32
Deg F
N/A
RW
-58 - 482
47144
AEM1 RTD6 Under2
Threshold
Int32
Deg F
N/A
RW
-58 - 482
47146
AEM1 RTD6 Over1
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47148
AEM1 RTD6 Over2
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47150
AEM1 RTD6 Under1
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47152
AEM1 RTD6 Under2
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47154
AEM1 RTD6 Out of
Range Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47156
AEM1 RTD7 Hysteresis
Int32
DeciPercent
Deci
RW
0 - 1000
47158
AEM1 RTD7 Arming
Delay
Int32
Second
N/A
RW
0 - 300
47160
AEM1 RTD7 Threshold1
Activation Delay
Int32
Second
N/A
RW
0 - 300
47162
AEM1 RTD7 Threshold2
Activation Delay
Int32
Second
N/A
RW
0 - 2
47164
AEM1 RTD7 Over1
Threshold
Int32
Deg F
N/A
RW
-58 - 482
47166
AEM1 RTD7 Over2
Threshold
Int32
Deg F
N/A
RW
-58 - 482
47168
AEM1 RTD7 Under1
Threshold
Int32
Deg F
N/A
RW
-58 - 482
47170
AEM1 RTD7 Under2
Threshold
Int32
Deg F
N/A
RW
-58 - 482
47172
AEM1 RTD7 Over1
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47174
AEM1 RTD7 Over2
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47176
AEM1 RTD7 Under1
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47178
AEM1 RTD7 Under2
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47180
AEM1 RTD7 Out of
Range Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47182
AEM1 RTD8 Hysteresis
Int32
DeciPercent
Deci
RW
0 - 1000
47184
AEM1 RTD8 Arming
Delay
Int32
Second
N/A
RW
0 - 300