Basler Electric DGC-2020 User Manual
Page 300
![background image](https://www.manualsdir.com/files/773941/content/doc300.png)
Figure 7-16. Settings Explorer, Programmable Senders, Oil Pressure Screen
Percent Fuel Level (Figure 7-17)
1. The percent fuel level sender is configured by selecting one of the sender types that come as a part
of the BESTCOMSPlus
® sender library by clicking on Load Fuel Settings File and selecting the
appropriate sender.
2. If no sender file matches the sender being used, the individual points that map resistance points to
fuel level may be modified by setting numeric values in the table, or dragging the points of the graph
to the desired characteristic. Information on sender characteristics should be obtained from the
sender manufacturer.
3. Select Positive or Negative sender slope as required for the desired sender graph.
4. Click Save Fuel Data to save the data in the current settings file.
5. If you want to save newly entered sender data as a sender library file, click Create Fuel Settings File
and enter a file name and location to save the file.
6. Click the Send Settings button in BESTCOMSPlus
® to send the sender settings to the DGC-2020.
7-12
DGC-2020 Setup
9400200990 Rev X