Basler Electric DGC-2020 User Manual

Page 133

background image

PGN Name

PGN

(Hex)

SPN

Parameter

Units

Scaling /

Offset

Bytes

Within

PGN
Data

Generator
Total AC
Reactive
Power

65028

(FE04)

2456

Generator Total Reactive Power

vars

n/a

1 to 4

2464

Generator Overall Power Factor

PF x

16,384

-1 offset

5 to 6

2518

Generator Overall Power Factor
Lagging

n/a

00=leading
01=lagging

10=error

11=not

available

7, bits

1 & 2

Generator
Total AC
Power

65029

(FE05)

2452

Generator Total Real Power

Watts

n/a

1 to 4

2460

Generator Total Apparent Power

VA

n/a

5 to 8

Generator
Average
Basic AC
Quantities

65030

(FE06)

2440

Generator Average L-L AC RMS
Voltage

Volts

n/a

1 to 2

2444

Generator Average L-N AC RMS
Voltage

Volts

n/a

3 to 4

2436

Generator Average AC
Frequency

Hz x

128

n/a

5 to 6

2448

Generator Average AC RMS
Current

Amps

n/a

7 to 8

Engine
Temperature

65262

(FEEE)

110

Engine Coolant Temperature (Not
sent when CAN is enabled)

°C

-40°C

offset

1

Engine Fluid
Level /
Pressure

65263

(FEEF)

100

Engine Oil Pressure (Not sent
when CAN is enabled)

kPa x

4

n/a

4

Dash Display

65276

(FEFC)

96

Fuel Level

% x

2.5

n/a

2

When the Engine Parameter Transmit

C

setting is enabled, the DGC-2020 broadcasts commands to the

ECU over CANBus. When the Engine Parameter Transmit setting is disabled, transmission of J1939
commands from the DGC-2020 to the engine are disabled, but commands from the engine to the DGC-
2020 are allowed.

Volvo Penta

Configuring the DGC-2020 for Volvo Penta

* necessitates the configuration of two additional settings:

Speed Select and Accelerator Position. The Speed Select setting

D

configures the Volvo Penta ECU to

operate the engine at the primary or secondary base speed. If the engine is configured by Volvo for 60 Hz
applications, the primary base speed is 1,800 rpm and the secondary base speed is 1,500 rpm. If the
engine is configured by Volvo for 50 Hz applications, the primary base speed is 1,500 rpm and the
secondary base speed is 1,800 rpm. The Accelerator Position setting

E

is expressed as a percentage and

tells the Volvo Penta ECU where to set the engine speed (trim) relative to the base speed. The range of
the setting is the base speed

±120 rpm. A setting of 0% will cause the engine to run at 120 rpm below the

base speed, a setting of 50% will cause the engine to run at the base speed, and a setting of 100% will
cause the engine to run at 120 rpm above the base speed. The Accelerator Position setting is linear with

9400200990 Rev X

DGC-2020 BESTCOMSPlus

® Software

4-23