Generator protection functions, Engine rpm -9, Engine run time -9 – Basler Electric DGC-2020 User Manual

Page 33: Maintenance timer -9, Fuel level -9, Generator protection functions -9, Overvoltage (59) and undervoltage (27) -9, Underfrequency (81u) and overfrequency (81o) -9, Reverse power (32) -9

background image

Engine RPM

Metering Range ................................ 0 to 4,500 rpm
Accuracy

* ......................................... ±2% of actual indication or ±2 rpm

Display Resolution ............................ 2 rpm
* When engine speed is below 2% of full-scale, reported rpm is 0.

Engine Run Time

Engine run time is retained in nonvolatile memory.

Metering Range ................................ 0 to 99,999 hours
Update Interval ................................. 6 min
Accuracy ...........................................

±1% of actual indication or ±12 min

Display Resolution ............................ 1 minute

Maintenance Timer

Maintenance timer indicates the time remaining until genset service is due. Value is retained in
nonvolatile memory.

Metering Range ................................ 0 to 5,000 hours
Update Interval ................................. 6 min
Accuracy ...........................................

±1% or actual indication or ±12 min

Display Resolution ............................ 1 minute

Fuel Level

Metering Range ................................ 0 to 100%
Accuracy ...........................................

±2% (subject to accuracy of sender)

Display Resolution ............................ 1.0%

Generator Protection Functions

Overvoltage (59) and Undervoltage (27)

Pickup Range ................................... 70 to 1,000 Vac
Pickup Increment .............................. 1 Vac
Inhibit Frequency Range .................. 20 to 400 Hz (27 function only)
Activation Delay Range .................... 0 to 30 s
Activation Delay Increment ............... 0.1 s

NOTE

The maximum voltage that can be safely applied to the DGC-2020 is 576 volts.
The pickup range is higher so that when the low-line override is used, and the
scale factor is 0.5 or less, effective protection levels of 500 volts can be
reached with a scale factor of 0.5.

Underfrequency (81U) and Overfrequency (81O)

Pickup Range ................................... 45 to 66 Hz (50/60 Hz nominal)

360 to 440 Hz (400 Hz nominal)

Pickup Increment .............................. 0.1 Hz (50/60 Hz nominal)

0.1 Hz (400 Hz nominal)

Activation Delay Range .................... 0 to 30 s
Activation Delay Increment ............... 0.1 s
Inhibit Voltage Range ....................... 70 to 576 Vac (81U function only)

Reverse Power (32)

Pickup Range ................................... –50 to 5% of Genset kW Rating
Pickup Increment .............................. 0.1%
Hysteresis Range ............................. 1 to 10% of Genset kW Rating
Hysteresis Increment ........................ 0.1%
Activation Delay Range .................... 0 to 30 s
Activation Delay Increment ............... 0.1 s

9400200990 Rev X

DGC-2020 General Information

1-9