beautypg.com

Remote module setup, Remote module setup -34, Figure 4-27. remote module setup -34 – Basler Electric DGC-2020 User Manual

Page 144: Load sharing module, Contact expansion module, Analog expansion module

background image

G

Alternate Frequency: Adjustable from 10 to 450 Hz in 0.01 Hz increments.

H

Rated Power Factor: Adjustable from –1 to +1 in increments of 0.0001.

I

Speed Signal Source: MPU, Gen Freq, or MPU Freq.

J

Rated Frequency: 50/60 or 400 Hz.

K

Rated Engine RPM: Adjustable from 750 to 3,600 in increments of 1.

L

Number Fly Wheel Teeth: Adjustable from 1 to 500 in increments of 0.1.

M

EPS Current Threshold: Adjustable from 3 to 10% of the CT primary rating in 1% increments.

N

Low Line Scale Factor: Adjustable from 0.001 to 3 in increments of 0.001.

O

System Units: English or Metric.

P

Metric Pressure Units: Bar or kPa/MPa.

Q

Battery Volts: 12 or 24 Vdc.

R

NFPA Level: 0 disables NFPA compliance, 1 enables Level 1 NFPA compliance, 2 enables Level 2.

S

Fuel Level Function: Disable, Fuel Lvl, Natural Gas, or Liquid Propane.

T

Source: Sender or ALG IN 1 through ALG IN 8.

U

Maximum Percent: Adjustable from 0 to 200% in 1% increments.

V

Minimum Percent: Adjustable from 0 to 200% in 1% increments.

W

Power Up Delay: Adjustable from 0 to 60 s in 1 s increments.

X

Generator Frequency: 50/60 Hz or 400 Hz.

Y

Calculated Values.

Z

Rated Volts (Low Line Scale Factor): Adjustable from 0.001 to 3.000 in increments of 0.001.

Remote Module Setup

The following settings are used to configure the LSM-2020, CEM-2020, and AEM-2020.

Load Sharing Module

A J1939 Address

A

must be entered when an optional LSM-2020 is enabled

B

. Use the LSM Auxiliary Input

Source setting

C

to select the source of the input values used for controlling the DGC-2020. If Local is

selected, the LSM-2020 uses its locally measured input values. If System Manager is selected, the LSM-
2020 uses the input values received through inter-genset communications from the unit designated as the
system manager. Note that the unit in the system with the lowest nonzero sequencing ID is the system
manager.

Contact Expansion Module

A J1939 Address

D

must be entered when the optional CEM-2020 is enabled

E

. Select number of CEM-

2020 outputs

F

.

Analog Expansion Module

A J1939 Address

G

must be entered when the optional AEM-2020 is enabled

H

.

The BESTCOMSPlus Remote Module Setup screen is illustrated in Figure 4-27.

Figure 4-27. Remote Module Setup

A

LSM J1939 Address: Adjustable from 1 to 253 in increments of 1.

B

Load Share Module: Enable or Disable.

C

LSM Auxiliary Input Source: Local or System Manager

D

CEM J1939 Address: Adjustable from 1 to 253 in increments of 1.

E

Contact Expansion Module: Enable or Disable.

F

CEM Outputs: 18 Outputs or 24 Outputs.

G

AEM J1939 Address: Adjustable from 1 to 253 in increments of 1.

4-34

DGC-2020 BESTCOMSPlus

® Software

9400200990 Rev X

This manual is related to the following products: