7. NFPA Level - Set this if NFPA level 1 or 2 compliance is required for the machine.
Figure 7-4. Settings Explorer, System Parameters, System Settings Screen
Rated Data (Figure 7-5) Note: Click the Edit button to change settings.
Front Panel Navigation Path: SETTINGS > SYSTEM PARAMS > SYSTEM SETTINGS
1. Generator Connection - Select WYE, DELTA, 1 PHASE A-B, 1 PHASE A-C, or GROUNDED DELTA
etc. based on the generator configuration.
2. Genset kW Rating - This parameter defines the kW rating of the machine.
3. Rated Volts - This parameter defines the voltage rating of the machine.
4. Rated Frequency - This parameter defines the frequency rating of the machine.
5. Rated Engine RPM - This parameter defines the engine rpm rating of the machine.
6. Rated Power Factor - This parameter defines the power factor rating of the machine.
7. Battery Voltage - Select 12 or 24.
Figure 7-5. Settings Explorer, System Parameters, Rated Data
Remote Module Setup (Figure 7-6)
Front Panel Navigation Path: SETTINGS > SYSTEM PARAMS > REMOTE MODULE SETUP
This screen is used to enable any I/O modules that are to be used with the DGC-2020. Refer to the
appropriate sections in the DGC-2020 manual for more details regarding the individual I/O modules.
Disable all if no modules are present.
7-4
DGC-2020 Setup
9400200990 Rev X