Basler Electric BE300PM User Manual
Instructions, Be300pm

www.basler.com
+1 618.654.2341 (USA)
Model
BE300PM
Part Number
9166800144
INTRODUCTION
The BE300PM static voltage regulator regulates voltage on
a 50- or 60-Hz generator with a brushless exciter and a
permanent magnet generator (PMG) excitation system.
ELECTRICAL SPECIFICATIONS
Output Power
Maximum Continuous: 3 Adc at 63 Vdc (190 W)
One-Minute Forcing:
5 Adc at 100 Vdc (500 W) with
240 Vac power input
Exciter Field DC Resistance
Minimum:
15 Ω
Input Power
Range:
171 to 264 Vac, single-phase
Frequency:
250 to 300 Hz, ±10%
Burden:
500 VA
Sensing Input
Range:
171 to 264 Vac, single-phase
Frequency:
50 to 75 Hz
Fuse
Bussmann GDC-4A or equivalent
Rating:
4 Aac, 250 Vac
Type:
Glass tube, 5 x 20 mm, time delay
Voltage Adjustment Range
171 to 264 Vac
Regulation Accuracy
Better than ±1.0%, no-load to full-load
EMI Suppression
Internal electromagnetic interference (EMI) filtering
Voltage Buildup
Automatic voltage buildup occurs for residual generator
voltages as low as 10 Vac.
Power Dissipation
8 W maximum
PHYSICAL SPECIFICATIONS
Temperature
Operating:
–40 to 60°C (–40 to 140°F)
Storage:
–40 to 85°C (–40 to 185°F)
Vibration
20 to 60 Hz with 0.035” displacement
1,000,000 cycles @ 30 Hz in all planes
Shock
Withstands 15 G in each of three perpendicular planes.
Moisture and Humidity
Tested per MIL-STD-705B, Method 711-1C
Salt Fog
Tested per ASTM B117-73
Weight
184 g (6.5 oz) net
Terminal Type
¼ inch male quick connect with insulating barrier
Agency Certification
Standard CSA-C22.2 No. 0 and 14
File LR 23131
OVEREXCITATION PROTECTION
If the exciter field voltage exceeds 85 to 90 Vdc, the
BE300PM automatically removes field power after a time
delay. This delay is inversely proportional to the field
voltage.
When field power is removed due to overexcitation, the
BE300PM will not reset or return to operation until the
generator output is interrupted.
CONTROLS
BE300PM controls consist of jumpers and screwdriver
adjusted potentiometers.
Potentiometer Controls
BE300PM potentiometer controls are accessible through
the controller front panel and are shown in Figure 1.
VOLT Control
This control raises and lowers the generator output voltage.
STAB Control
This control adjusts the stability by increasing and
decreasing the response time of the BE300PM.
U/F Control
This control adjusts the corner frequency point of the
BE300PM frequency compensation characteristic.
Optional Remote Voltage Adjust Rheostat
If remote adjustment of the generator output is desired, the
Voltage Adjust Rheostat jumper must be replaced with a
user-supplied rheostat. A 2,000 ohm, ½ watt rheostat will
provide ±10% voltage adjustment. For ±5% voltage
adjustment, use a 1,000 ohm, ½ watt rheostat. Figure
shows the proper remote rheostat connections. Refer to
Operating Procedures for instructions on setting up the
remote rheostat.
Jumpers
Two jumpers control BE300PM operation: the Corner
Frequency jumper and the Voltage Adjust Rheostat jumper.
These jumpers are shown in Figure 3.
Corner Frequency Jumper
BE300PM controllers are delivered with the nominal corner
frequency preset to 58 hertz in the 60 hertz mode. For 50
hertz operation, and a nominal corner frequency of 48
hertz, the Corner Frequency jumper must be moved to the
50 Hz terminal.
Voltage Adjust Rheostat Jumper
BE300PM controllers are delivered with the Voltage Adjust
Rheostat jumper connected across terminals 6 and 7. This
enables adjustment of the generator output voltage through
Publication
9166800894
Revision
B
Instructions
Date
01/13
Copyright
2013