Enable lsm-2020, cem-2020, and aem-2020, Programmable inputs, Enable lsm-2020, cem-2020, and aem-2020 -16 – Basler Electric DGC-2020 User Manual
Page 304: Programmable inputs -16, Configuration instructions -16

Enable LSM-2020, CEM-2020, and AEM-2020
Front Panel Navigation Path: SETTINGS > SYSTEM PARAMS > REMOTE MODULE SETUP
The parameters for remote inputs and remote outputs are disabled and cannot be configured in
BESTCOMSPlus
® until after the appropriate module has been enabled. Thus, expansion modules
connected to the DGC-2020 must be enabled before the associated parameters can be modified. See
Figure 7-21.
Figure 7-21. Settings Explorer, System Parameters, Remote Module Setup Screen
Configure the following parameters:
1. Load Share Module Enable/Disable - Select Enable if a load share module is present in the system.
2. LSM J1939 Address - Enter the J1939 address to be used by the LSM-2020. Normally this will not
have to be changed unless the address is already in use elsewhere on the CAN bus network.
3. LSM Auxiliary Input Source – Select Local if locally measured input values are to be used. Select
System Manager if the measured input values of the unit designated as the system manager are to
be used.
4. Contact Expansion Module Enable/Disable - Select Enable if a contact expansion module is present
in the system.
5. CEM J1939 Address - Set the J1939 address to be used by the CEM-2020. Normally this will not
have to be changed unless the address is already in use elsewhere on the CAN bus network.
6. CEM Outputs - This setting defines the number of output relays on the CEM-2020. Select 18 or 24.
Refer to the style chart in Section 1, General Information, of the DGC-2020 instruction manual to
determine if you have 18 or 24 output relays on the CEM-2020.
Programmable Inputs
The programmable inputs consist of:
•
Contact inputs on the DGC-2020.
•
Programmable functions on the DGC-2020. The programmable functions allow mapping of
particular inputs to certain functions. For example, one can select an input for the ATS (Automatic
Transfer Switch) input function, or a Low Fuel Level indication function.
•
Remote LSM inputs on the LSM-2020. The LSM-2020 has one analog input.
•
Remote contact inputs on the CEM-2020.
•
Remote analog inputs on the AEM-2020.
•
Remote RTD inputs on the AEM-2020.
•
Remote thermocouple inputs on the AEM-2020.
Configuration Instructions
Configuring contact inputs on the DGC-2020 (See Figure 7-22.)
Front Panel Navigation Path: SETTINGS > PROGRAMMABLE INPUTS > CONFIGURABLE INPUTS
7-16
DGC-2020 Setup
9400200990 Rev X