beautypg.com

Modem dialout conditions 1, Modem dialout conditions 2, Reserved – Basler Electric DGC-2020 User Manual

Page 456: Can bus enable

background image

B-24

DGC-2020 Modbus

™ Communication

9400200990 Rev X

Register

Description

Type

Units

Scaling

Factor

R/W

Range

44024-25

Modem Dialout Conditions 1

Uint32

N/A

N/A

RW

Bit 0 = Aux Input 5 Closed
Bit 1 = Aux Input 4 Closed
Bit 2 = Aux Input 3 Closed
Bit 3 = Aux Input 2 Closed
Bit 4 = Aux Input 1 Closed
Bit 5 = Cooldown Timer Active
Bit 6 = Switch Not In Auto
Bit 7 = Scheduled Maintenance Pre-
Alarm
Bit 8 = Weak Battery Voltage Pre-Alarm
Bit 9 = Low Battery Voltage Pre-Alarm
Bit 10 = Low Oil Pressure Pre-Alarm
Bit 11 = High Coolant Temp Pre-Alarm
Bit 12 = kW Overload 1 Pre-Alarm
Bit 13 = Battery Overvoltage Pre-Alarm
Bit 14 = Fuel Level Sender Fail Pre-
Alarm
Bit 15 = Oil Pressure Sender Fail Pre-
Alarm
Bit 16 = Coolant Temp Sender Fail Pre-
Alarm
Bit 17 = Low Coolant Temp Pre-Alarm
Bit 18 = High Fuel Pre-Alarm
Bit 19 = Low Fuel Pre-Alarm
Bit 20 = Overspeed Alarm
Bit 21 = Emergency Stop Alarm
Bit 22 = Overcrank Alarm
Bit 23 = Low Coolant Level Status
Bit 24 = Low Fuel Alarm
Bit 25 = Loss of Gen Volt Sensing Alarm
Bit 26 = MPU Speed Sender Fail Alarm
Bit 27 = Fuel Level Sender Fail Alarm
Bit 28 = Oil Pressure Sender Fail Alarm
Bit 29 = Coolant Temp Sender Fail
Alarm
Bit 30 = Low Oil Pressure Alarm
Bit 31 = High Coolant Temp Alarm

44026-27

Modem Dialout Conditions 2

Uint32

N/A

N/A

RW

Bit 0 = 59-2 Trip Alarm
Bit 1 = 27-2 Trip Alarm
Bit 2 = 51-2 Trip Alarm
Bit 3 = Engine Running
Bit 4 = Battery Charger Fail Status
Bit 5 = Fuel Leak Detect Status
Bit 6 = Transfer Fail Alarm
Bit 7 = 81U Trip Pre-Alarm
Bit 8 = 81O Trip Pre-Alarm
Bit 9 = 59-1 Trip Pre-Alarm
Bit 10 = 27-1 Trip Pre-Alarm
Bit 11 = 47 Trip Pre-Alarm
Bit 12 = 51-1 Trip Pre-Alarm
Bit 13 = 81U Trip Alarm
Bit 14 = 81O Trip Alarm
Bit 15 = 59-1 Trip Alarm
Bit 16 = 27-1 Trip Alarm
Bit 17 = 47 Trip Alarm
Bit 18 = 51-1 Trip Alarm
Bit 19 = Loss of ECU Coms Pre-Alarm
Bit 20 = Loss of ECU Coms Alarm
Bit 21 = Aux Input 16 Closed
Bit 22 = Aux Input 15 Closed
Bit 23 = Aux Input 14 Closed
Bit 24 = Aux Input 13 Closed
Bit 25 = Aux Input 12 Closed
Bit 26 = Aux Input 11 Closed
Bit 27 = Aux Input 10 Closed
Bit 28 = Aux Input 9 Closed
Bit 29 = Aux Input 8 Closed
Bit 30 = Aux Input 7 Closed
Bit 31 = Aux Input 6 Closed

44028-30

RESERVED

44032

CAN bus Enable

Int32

N/A

N/A

RW

0 = Disable
1 = Enable

This manual is related to the following products: