Alarm configuration -8 – Basler Electric DGC-2020 User Manual
Page 296
![background image](https://www.manualsdir.com/files/773941/content/doc296.png)
Figure 7-10. Settings Explorer, System Parameters, Auto Config Detection Screen
Alarm Configuration
Horn Configuration (Figure 7-11)
Front Panel Navigation Path: SETTINGS > ALARM CONFIGURATION > HORN CONFIGURATION
1. Horn Enable - This setting enables or disables the output for the external alarm horn.
2. Not In Auto Horn Enable - This setting enables or disables the horn when not in auto mode.
Figure 7-11. Settings Explorer, Alarm Configuration, Horn Configuration Screen
Pre-Alarms
Front Panel Navigation Path: SETTINGS > ALARM CONFIGURATION > PRE-ALARMS
Examine each of the pre-alarms. Pre-alarm setup is not required to operate the machine, but is likely to
be desired to provide warnings for machine protection. Enable any desired pre-alarms and enter an
appropriate threshold. Set the activation delay where possible. The activation delay is the duration that a
condition remains in effect before annunciating a pre-alarm. Refer to the appropriate paragraphs in
Section 4, BESTCOMSPlus
® Software, for additional information regarding pre-alarm configuration. See
7-8
DGC-2020 Setup
9400200990 Rev X