Basler Electric DGC-2020 User Manual
Page 558
B-126
DGC-2020 Modbus
™ Communication
9400200990 Rev X
Holding
Register
Parameter
Range
Read/Write
Supported
Data
Format
Units
40120
3 Phase Apparent Power(b)
R
DP
KVA
40121
Phase a Power(a)
R
DP
KWatt x 10000
40122
Phase a Power(b)
R
DP
KWatt
40123
Phase b Power(a)
R
DP
KWatt x 10000
40124
Phase b Power(b)
R
DP
KWatt
40125
Phase c Power(a)
R
DP
KWatt x 10000
40126
Phase c Power(b)
R
DP
KWatt
40127
3 Phase power(a)
R
DP
KWatt x 10000
40128
3 Phase power(b)
R
DP
KWatt
40129
3 Phase Total kW-Hours(a)
R W
TP
KWH x 10000 x
10000
40130
3 Phase Total kW-Hours(b)
R W
TP
KWH x 10000
40131
3 Phase Total kW-Hours(x)
R W
TP
KWH
40132
Power Factor
0-100
R
0.01
40133
Frequency
R
0.1 Hertz
40134
Present Total kW-minutes (a)
R W
TP
kWm x 10000 x
10000
40135
Present Total kW-minutes (b)
R W
TP
kWm x 10000
40136
Present Total kW-minutes (c)
R W
TP
kWm
40137
Generator Speed Mode
individual bits
are 0 or 1
R W
active spd signals:
b0 =mag. pick-up or CAN’s ECU
engine’s speed.
b1 =generator
40138-39
RESERVED
40140
Power Factor State
0-3
R
0 = leading, 1 = lagging
40141-272
RESERVED
40273
Input Contacts States
individual bits
are 0 or 1
R
b0 = coolant level,
b1 = ATS,
b2 = E-stop,
b3 = charger failed,
b4 = aux. input 1,
b5 = aux. input 2,
b6 = aux. input 3,
b7 = aux. input 4.
/* b7 =
aux. input 4. */
40274
BESTCOMSPlus
® Test Buttons
States
individual bits
are 0 or 1
R W
b0 = button #1,
b1 = button #2,
b2 = button #3,
b3 = button #4,
b4-b7 are not used.
40275-80
RESERVED
40281
Embedded Code Version Number
(a)
0-99
R
40282
Embedded Code Version Number
(b)
0-9999
R
40283
Embedded Code Version Number
(c)
0-9999
R
40287-97
RESERVED