B-126

DGC-2020 Modbus

™ Communication

9400200990 Rev X

Holding

Register

Parameter

Range

Read/Write

Supported

Data

Format

Units

40120

3 Phase Apparent Power(b)

R

DP

KVA

40121

Phase a Power(a)

R

DP

KWatt x 10000

40122

Phase a Power(b)

R

DP

KWatt

40123

Phase b Power(a)

R

DP

KWatt x 10000

40124

Phase b Power(b)

R

DP

KWatt

40125

Phase c Power(a)

R

DP

KWatt x 10000

40126

Phase c Power(b)

R

DP

KWatt

40127

3 Phase power(a)

R

DP

KWatt x 10000

40128

3 Phase power(b)

R

DP

KWatt

40129

3 Phase Total kW-Hours(a)

R W

TP

KWH x 10000 x
10000

40130

3 Phase Total kW-Hours(b)

R W

TP

KWH x 10000

40131

3 Phase Total kW-Hours(x)

R W

TP

KWH

40132

Power Factor

0-100

R

0.01

40133

Frequency

R

0.1 Hertz

40134

Present Total kW-minutes (a)

R W

TP

kWm x 10000 x
10000

40135

Present Total kW-minutes (b)

R W

TP

kWm x 10000

40136

Present Total kW-minutes (c)

R W

TP

kWm

40137

Generator Speed Mode

individual bits
are 0 or 1

R W

active spd signals:
b0 =mag. pick-up or CAN’s ECU
engine’s speed.
b1 =generator

40138-39

RESERVED

40140

Power Factor State

0-3

R

0 = leading, 1 = lagging

40141-272

RESERVED

40273

Input Contacts States

individual bits
are 0 or 1

R

b0 = coolant level,
b1 = ATS,
b2 = E-stop,
b3 = charger failed,
b4 = aux. input 1,
b5 = aux. input 2,
b6 = aux. input 3,
b7 = aux. input 4.

/* b7 =

aux. input 4. */

40274

BESTCOMSPlus

® Test Buttons

States

individual bits
are 0 or 1

R W

b0 = button #1,
b1 = button #2,
b2 = button #3,
b3 = button #4,
b4-b7 are not used.

40275-80

RESERVED

40281

Embedded Code Version Number
(a)

0-99

R

40282

Embedded Code Version Number
(b)

0-9999

R

40283

Embedded Code Version Number
(c)

0-9999

R

40287-97

RESERVED