beautypg.com

Basler Electric DGC-2020 User Manual

Page 450

background image

B-18

DGC-2020 Modbus

™ Communication

9400200990 Rev X

Register

Description

Type

Units

Scaling

Factor

R/W

Range

43456

Battery Charge Failed Contact Input

Int32

N/A

N/A

RW

-1 = None
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
4 = Input 5
5 = Input 6
6 = Input 7
7 = Input 8
8 = Input 9
9 = Input 10
10 = Input 11
11 = Input 12
12 = Input 13
13 = Input 14
14 = Input 15
15 = Input 16

43458

Battery Charge Failed Config Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm

43460

Battery Charge Failed Time Delay

Int32

Second

N/A

RW

0 - 300

43462

Fuel Leak Detect Contact Input

Int32

N/A

N/A

RW

-1 = None
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
4 = Input 5
5 = Input 6
6 = Input 7
7 = Input 8
8 = Input 9
9 = Input 10
10 = Input 11
11 = Input 12
12 = Input 13
13 = Input 14
14 = Input 15
15 = Input 16

43464

Fuel Leak Detect Config Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm

43466

Fuel Leak Detect Time Delay

Int32

Second

N/A

RW

0 - 300

43468

User Configurable Input 1 Eng Run Only

Int32

N/A

N/A

RW

0 = Always
1 = While
Engine
Running Only

43470

User Configurable Input 2 Eng Run Only

Int32

N/A

N/A

RW

0 = Always
1 = While
Engine
Running Only

43472

User Configurable Input 3 Eng Run Only

Int32

N/A

N/A

RW

0 = Always
1 = While
Engine
Running Only

43474

User Configurable Input 4 Eng Run Only

Int32

N/A

N/A

RW

0 = Always
1 = While
Engine
Running Only

43476

User Configurable Input 5 Eng Run Only

Int32

N/A

N/A

RW

0 = Always
1 = While
Engine
Running Only

43478

User Configurable Input 6 Eng Run Only

Int32

N/A

N/A

RW

0 = Always
1 = While
Engine
Running Only

This manual is related to the following products: