Basler Electric DGC-2020 User Manual
Page 450

B-18
DGC-2020 Modbus
™ Communication
9400200990 Rev X
Register
Description
Type
Units
Scaling
Factor
R/W
Range
43456
Battery Charge Failed Contact Input
Int32
N/A
N/A
RW
-1 = None
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
4 = Input 5
5 = Input 6
6 = Input 7
7 = Input 8
8 = Input 9
9 = Input 10
10 = Input 11
11 = Input 12
12 = Input 13
13 = Input 14
14 = Input 15
15 = Input 16
43458
Battery Charge Failed Config Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
43460
Battery Charge Failed Time Delay
Int32
Second
N/A
RW
0 - 300
43462
Fuel Leak Detect Contact Input
Int32
N/A
N/A
RW
-1 = None
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
4 = Input 5
5 = Input 6
6 = Input 7
7 = Input 8
8 = Input 9
9 = Input 10
10 = Input 11
11 = Input 12
12 = Input 13
13 = Input 14
14 = Input 15
15 = Input 16
43464
Fuel Leak Detect Config Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
43466
Fuel Leak Detect Time Delay
Int32
Second
N/A
RW
0 - 300
43468
User Configurable Input 1 Eng Run Only
Int32
N/A
N/A
RW
0 = Always
1 = While
Engine
Running Only
43470
User Configurable Input 2 Eng Run Only
Int32
N/A
N/A
RW
0 = Always
1 = While
Engine
Running Only
43472
User Configurable Input 3 Eng Run Only
Int32
N/A
N/A
RW
0 = Always
1 = While
Engine
Running Only
43474
User Configurable Input 4 Eng Run Only
Int32
N/A
N/A
RW
0 = Always
1 = While
Engine
Running Only
43476
User Configurable Input 5 Eng Run Only
Int32
N/A
N/A
RW
0 = Always
1 = While
Engine
Running Only
43478
User Configurable Input 6 Eng Run Only
Int32
N/A
N/A
RW
0 = Always
1 = While
Engine
Running Only