Mtu module type, Mtu speed demand switch, Mtu rpm request for engine – Basler Electric DGC-2020 User Manual
Page 562
B-130
DGC-2020 Modbus
™ Communication
9400200990 Rev X
Holding
Register
Parameter
Range
Read/Write
Supported
Data
Format
Units
40372
CAN Communications Diagnostics
for use when CAN is enabled.
individual bits
are 0 or 1
R
Bit 12 - .Engine Run Time
Bit 11 – Data Failure Status Previous
Active DTCs Cleared
Bit 10 – Active DTCs Cleared
Bit 9 - Previous Active DTCs
Bit 8 - Current Active DTCs
Bit 7 – Coolant Level
Bit 6 - Oil Pressure
Bit 5 - Coolant Temp
Bit 4 - Engine Speed
Bit 3 – Can Error Status tx err passive
Bit 2 – Can Error Status rx err passive
Bit 1 – Can Error Status driver sleep
status
Bit 0 – Can Error Status bus off
40373
System Config
individual bits
are 0 or 1
R W
Bit 0 – RUN
Bit 1 – OFF
Bit 2 – AUTO_RUN
Bit 3 – AUTO_OFF
Bit 4 – AUTO_ANY
40374
System Status
0 - 10
R
0 = RESET
1 = READY
2 = CRANKING
3 = RESTING
4 = RUNNING
5 = ALARM
6 = PRESTART
7 = COOLING
8 = CONNECTING
9 = DISCONNECT
10 = PULSING
11 = UNLOADING
40375
Used to display Value, NC, NS,
NA, and SF
R
Bits 0-2: coolant level
Bits 3-5: coolant temperature
Bits 6-8: oil pressure
Bits 9-11: engine speed
Bits 12-14: engine run time
Bit 15: NOT USED
3-Bit Status Flag Values:
000 for Valid Data
001 for No Comms
010 for Not Sent
011 for Not Supp
100 for Sender Error
40380-81
FUTURE USE
40382
MTU module type
1-4
R W
1 = module type 201
2 = module type 302
3 = module type 303
4 = module type 304
40383
MTU speed demand switch
0-7
R W
0 = ANALOG_CAN
1 = UP_DN_ECU
2 = UP_DN_CAN
3 = ANALOG_ECU
5 = FREQUENCY
7 = NO_CAN_DEMAND
40384
MTU RPM request for engine
1400-2000
R W
40385
Volvo Accelerator Pedal Position
(Trim)
0-100
R W
0 = Rated speed – 120rpm;
50 = Rated speed;
100 = Rated speed + 120rpm.
40386
Volvo Engine RPM Select
0-1
R W
0 = Primary,
1 = Secondary.
40387
J1939 source address for this unit
0-253
R W
40388
CAN bus ECU Configuration
0-65535
R W
0 = Not configured;
1 = Volvo Penta EDC3;
2 = MTU MDEC
3 = MTU ADEC