3 phase overcurrent pickup(51-3), 3 phase overcurrent time dial (51-3), 3 phase overcurrent curve(51-3) – Basler Electric DGC-2020 User Manual
Page 463: 3 phase overcurrent alarm configuration (51-3), 1 phase overcurrent pickup(51-3), 1 phase overcurrent time dial (51-3), 1 phase overcurrent curve(51-3), 1 phase overcurrent alarm configuration (51-3)

9400200990 Rev X
DGC-2020 Modbus
™ Communication
B-31
Register
Description
Type
Units
Scaling
Factor
R/W
Range
44438
51-1 Curve Constant N
Float
N/A
N/A
RW
0.5 - 2.5
44440
51-1 Curve Constant R
Float
N/A
N/A
RW
0 - 30
44442
51-2 Curve Constant A
Float
N/A
N/A
RW
0 - 600
44444
51-2 Curve Constant B
Float
N/A
N/A
RW
0 - 25
44446
51-2 Curve Constant C
Float
N/A
N/A
RW
0 - 1
44448
51-2 Curve Constant N
Float
N/A
N/A
RW
0.5 - 2.5
44450
51-2 Curve Constant R
Float
N/A
N/A
RW
0 - 30
44452
3 Phase Overcurrent Pickup
(51-3)
Uint32
CentiAmp
Centi
RW
18 - 775
44454
3 Phase Overcurrent Time Dial
(51-3)
Uint32
DeciUnit
Deci
RW
0 - 72000
44456
3 Phase Overcurrent Curve
(51-3)
Uint32
N/A
N/A
RW
0 = S1 Curve
1 = S2 Curve
2 = L1 Curve
3 = L2 Curve
4 = D Curve
5 = M Curve
6 = I1 Curve
7 = I2 Curve
8 = V1 Curve
9 = V2 Curve
10 = E1 Curve
11 = E2 Curve
12 = A Curve
13 = B Curve
14 = C Curve
15 = G Curve
16 = F Curve
17 = Programmable
44458
3 Phase Overcurrent Alarm
Configuration (51-3)
Uint32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
44460
1 Phase Overcurrent Pickup
(51-3)
Uint32
CentiAmp
Centi
RW
18 - 775
44462
1 Phase Overcurrent Time Dial
(51-3)
Uint32
DeciUnit
Deci
RW
0 - 72000
44464
1 Phase Overcurrent Curve
(51-3)
Uint32
N/A
N/A
RW
0 = S1 Curve
1 = S2 Curve
2 = L1 Curve
3 = L2 Curve
4 = D Curve
5 = M Curve
6 = I1 Curve
7 = I2 Curve
8 = V1 Curve
9 = V2 Curve
10 = E1 Curve
11 = E2 Curve
12 = A Curve
13 = B Curve
14 = C Curve
15 = G Curve
16 = F Curve
17 = Programmable
44466
1 Phase Overcurrent Alarm
Configuration (51-3)
Uint32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
44468
Overcurrent Low Line Scale
Factor (51-3)
Float
N/A
N/A
RW
0.001 - 3
44470
3 Phase Overcurrent Reset
Type (51-3)
Int32
N/A
N/A
RW
0 = Instantaneous
1 = Integrating
44472
1 Phase Overcurrent Reset
Type (51-3)
Int32
N/A
N/A
RW
0 = Instantaneous
1 = Integrating
44474
51-3 Curve Constant A
Float
N/A
N/A
RW
0 - 600
44476
51-3 Curve Constant B
Float
N/A
N/A
RW
0 - 25
44478
51-3 Curve Constant C
Float
N/A
N/A
RW
0 - 1