Cumulative number of engine starts, Session start date month, Session start date day – Basler Electric DGC-2020 User Manual
Page 474: Session start date year, Generator status, 8 = connecting state, Contact status
B-42
DGC-2020 Modbus
™ Communication
9400200990 Rev X
Register
Description
Type
Units
Scaling
Factor
R/W
Range
44868
Session Unloaded
Engine Run Min.
Int32
N/A
N/A
R
0 - 59
44870
Session kW-Hrs
Int32
KiloWattHour
N/A
R
0 - 999999999
44872
Cumulative Number of
Engine Starts
Uint32
N/A
N/A
RW
0 - 65535
44874
Session Start Date
Month
Uint32
N/A
N/A
RW
1 - 12
44876
Session Start Date Day
Uint32
N/A
N/A
RW
1 - 31
44878
Session Start Date Year
Uint32
N/A
N/A
RW
0 - 99
44880
Generator Status
Uint32
N/A
N/A
R
0 = RESET State
1 = READY State
2 = CRANKING State
3 = RESTING State
4 = RUNNING State
5 = ALARM State
6 = PRESTART State
7 = COOLING State
8 = CONNECTING State
9 = DISCONNECT State
10 = PULSING State
11 = UNLOADING State
44882
Contact Status
Uint32
N/A
N/A
R
Bit 0 = Not Used
Bit 1 = Not Used
Bit 2 = Not Used
Bit 3 = Not Used
Bit 4 = Not Used
Bit 5 = Not Used
Bit 6 = Not Used
Bit 7 = Not Used
Bit 8 = Not Used
Bit 9 = Not Used
Bit 10 = Not Used
Bit 11 = Not Used
Bit 12 = Input 16
Bit 13 = Input 15
Bit 14 = Input 14
Bit 15 = Input 13
Bit 16 = Input 12
Bit 17 = Input 11
Bit 18 = Input 10
Bit 19 = Input 9
Bit 20 = Input 8
Bit 21 = Input 7
Bit 22 = Input 6
Bit 23 = Input 5
Bit 24 = Input 4
Bit 25 = Input 3
Bit 26 = Input 2
Bit 27 = Input 1
Bit 28 = Reserved
Bit 29 = Estop
Bit 30 = Not Used
Bit 31 = Not Used