Rear panel, Rear panel -27 – Basler Electric DGC-2020 User Manual
Page 67
Transferring to Mains: Load is being transferred to the mains bus.
Disabled: DGC-2020 is in the OFF or RUN operating mode or in the alarm state.
Transfer Delay: Displays the current timer value in seconds.
Return Delay: Displays the current timer value in seconds.
Max Transfer Time: Displays the current timer value in seconds.
Max Parallel Time: Displays the current timer value in seconds.
Open Transition Delay: Displays the current timer value in seconds.
Note
The Mains Fail Transfer screen found at Metering > Alarms-Status >
Mains Fail Transfer only shows timers that are actively counting and
are relevant to mains fail transfer. They are not otherwise visible.
Rear Panel
All DGC-2020 terminals and connectors are located on the rear panel. Rear panel terminals and
connectors, for hardware version 3, are illustrated in Figure 2-6. Table 2-2 lists the call-outs of Figure 2-6
along with a description of each connector type. Rear panel terminals and connectors, for hardware
versions 1 and 2, are illustrated in Figure 2-7. Table 2-3 lists the call-outs of Figure 2-7 along with a
description of each connector type. The DGC-2020 rear panel is shown in Figure 2-6 and Figure 2-7 with
the rear cover removed.
9400200990 Rev X
DGC-2020 Human-Machine Interface
2-27