9400200990 Rev X

DGC-2020 Modbus

™ Communication

B-121

Register

Description

Type

Units

Scaling

Factor

R/W

Range

47186

AEM1 RTD8 Threshold1
Activation Delay

Int32

Second

N/A

RW

0 - 300

47188

AEM1 RTD8 Threshold2
Activation Delay

Int32

Second

N/A

RW

0 - 2

47190

AEM1 RTD8 Over1
Threshold

Int32

Deg F

N/A

RW

-58 - 482

47192

AEM1 RTD8 Over2
Threshold

Int32

Deg F

N/A

RW

-58 - 482

47194

AEM1 RTD8 Under1
Threshold

Int32

Deg F

N/A

RW

-58 - 482

47196

AEM1 RTD8 Under2
Threshold

Int32

Deg F

N/A

RW

-58 - 482

47198

AEM1 RTD8 Over1
Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only

47200

AEM1 RTD8 Over2
Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only

47202

AEM1 RTD8 Under1
Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only

47204

AEM1 RTD8 Under2
Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only

47206

AEM1 RTD8 Out of
Range Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only

47208-48

RESERVED

47250

AEM1 Thermocouple1
Hysteresis

Int32

DeciPercent

Deci

RW

0 - 1000

47252

AEM1 Thermocouple1
Arming Delay

Int32

Second

N/A

RW

0 - 300

47254

AEM1 Thermocouple1
Threshold1 Activation
Delay

Int32

Second

N/A

RW

0 - 300

47256

AEM1 Thermocouple1
Threshold2 Activation
Delay

Int32

Second

N/A

RW

0 - 300

47258

AEM1 Thermocouple1
Over1 Threshold

Int32

Deg F

N/A

RW

32 - 2507

47260

AEM1 Thermocouple1
Over2 Threshold

Int32

Deg F

N/A

RW

32 - 2507

47262

AEM1 Thermocouple1
Under1 Threshold

Int32

Deg F

N/A

RW

32 - 2507

47264

AEM1 Thermocouple1
Under2 Threshold

Int32

Deg F

N/A

RW

32 - 2507

47266

AEM1 Thermocouple1
Over1 Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only

47268

AEM1 Thermocouple1
Over2 Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only

47270

AEM1 Thermocouple1
Under1 Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only