B-38

DGC-2020 Modbus

™ Communication

9400200990 Rev X

Register

Description

Type

Units

Scaling

Factor

R/W

Range

44820-21

Sender Fail Alarm
Metering

Int32

N/A

N/A

R

Bit 0 = Not Used
Bit 1 = Not Used
Bit 2 = Not Used
Bit 3 = Not Used
Bit 4 = Not Used
Bit 5 = Not Used
Bit 6 = Not Used
Bit 7 = Not Used
Bit 8 = Not Used
Bit 9 = Not Used
Bit 10 = Not Used
Bit 11 = Not Used
Bit 12 = Not Used
Bit 13 = Not Used
Bit 14 = Not Used
Bit 15 = Not Used
Bit 16 = Not Used
Bit 17 = Not Used
Bit 18 = Not Used
Bit 19 = Not Used
Bit 20 = Not Used
Bit 21 = Not Used
Bit 22 = Not Used
Bit 23 = Not Used
Bit 24 = Not Used
Bit 25 = Not Used
Bit 26 = Not Used
Bit 27 = Generator Voltage
Bit 28 = Fuel Level
Bit 29 = Coolant Temp
Bit 30 = Oil Pressure
Bit 31 = Speed

44822

Gen Protect Status

Int32

N/A

N/A

R

Bit 0 = Not Used
Bit 1 = Not Used
Bit 2 = Not Used
Bit 3 = Not Used
Bit 4 = Not Used
Bit 5 = Not Used
Bit 6 = Not Used
Bit 7 = Not Used
Bit 8 = Not Used
Bit 9 = Not Used
Bit 10 = Not Used
Bit 11 = Not Used
Bit 12 = Not Used
Bit 13 = Not Used
Bit 14 = Not Used
Bit 15 = Not Used
Bit 16 = Not Used
Bit 17 = Not Used
Bit 18 = 81 ROC DF/DT Trip
Bit 19 = 78 Vector Shift Trip
Bit 20 = 51-3 Overcurrent
Bit 21 = 40Q Loss of Excitation
Bit 22 = 32 Reverse Power
Bit 23 = 59-2 Overvoltage
Bit 24 = 27-2 Undervoltage
Bit 25 = 51-2 Overcurrent
Bit 26 = 81 Underfrequency
Bit 27 = 81 Overfrequency
Bit 28 = 59-1 Overvoltage
Bit 29 = 27-1 Undervoltage
Bit 30 = 47 Phase Imbalance
Bit 31 = 51-1 Overcurrent