Connectors and headers may contain tin- or gold-plated conductors. Tin-plated conductors are housed in
a black plastic casing and gold-plated conductors are housed in an orange plastic casing. Mate
connectors to headers of the same color only.
Connector screw terminals accept a maximum wire size of 12 AWG. Maximum screw torque is 5 inch-
pounds (0.56 N
•m).
Operating Power
The Contact Expansion Module operating power input accepts either 12 Vdc or 24 Vdc and tolerates
voltage over the range of 6 to 32 Vdc. Operating power must be of the correct polarity. Although reverse
polarity will not cause damage, the CEM-2020 will not operate. Operating power terminals are listed in
Table 10-1.
It is recommended that a fuse be added for additional protection for the wiring to the battery input of the
Contact Expansion Module. A Bussmann ABC-7 fuse or equivalent is recommended.
Table 10-1. Operating Power Terminals
Terminal
Description
P1-
(SHIELD)
Chassis ground connection
P1- – (BATT–)
Negative side of operating power input
P1- + (BATT+)
Positive side of operating power input
Contact Inputs and Contact Outputs
The CEM-2020 (Figure 10-3) has 10 contact inputs and 24 contact outputs. The CEM-2020H (Figure
10-4) has 10 contact inputs and 18 contact outputs.
NOTE
To follow UL guidelines, a fuse must be implemented in the 2Adc contact
circuits (Outputs 13 through 24) of the CEM-2020H used in hazardous
locations. The suggested fuse size in Adc = (100/Contact Voltage) with a
maximum fuse size of 5Adc.