Connectors and headers may contain tin- or gold-plated conductors. Tin-plated conductors are housed in
a black plastic casing and gold-plated conductors are housed in an orange plastic casing. Mate
connectors to headers of the same color only.

Connector screw terminals accept a maximum wire size of 12 AWG. Maximum screw torque is 5 inch-
pounds (0.56 N

•m).

Operating Power

The Contact Expansion Module operating power input accepts either 12 Vdc or 24 Vdc and tolerates
voltage over the range of 6 to 32 Vdc. Operating power must be of the correct polarity. Although reverse
polarity will not cause damage, the CEM-2020 will not operate. Operating power terminals are listed in
Table 10-1.

It is recommended that a fuse be added for additional protection for the wiring to the battery input of the
Contact Expansion Module. A Bussmann ABC-7 fuse or equivalent is recommended.

Table 10-1. Operating Power Terminals

Terminal

Description

P1-

(SHIELD)

Chassis ground connection

P1- – (BATT–)

Negative side of operating power input

P1- + (BATT+)

Positive side of operating power input

Contact Inputs and Contact Outputs

The CEM-2020 (Figure 10-3) has 10 contact inputs and 24 contact outputs. The CEM-2020H (Figure
10-4)
has 10 contact inputs and 18 contact outputs.

NOTE

To follow UL guidelines, a fuse must be implemented in the 2Adc contact
circuits (Outputs 13 through 24) of the CEM-2020H used in hazardous
locations. The suggested fuse size in Adc = (100/Contact Voltage) with a
maximum fuse size of 5Adc.

10-6

DGC-2020 CEM-2020 (Contact Expansion Module)

9400200990 Rev X