Figure 7-28. Settings Explorer, Programmable Inputs, Remote Thermocouple Inputs Screen

Configure the following parameters:

1. Label Text - Enter descriptive text that signifies the use of the input. This text appears next to the

input status and associated alarm and pre-alarm status in BESTlogicPlus Programmable Logic and in
the event log when the input thresholds are configured as an Alarm or Pre-Alarm.

2. Hysteresis (%) - Enter a value for the desired hysteresis for threshold detection. Hysteresis helps

prevent intermittent detection of thresholds.

3. Arming Delay - The arming delay is the wait time after engine startup, before input monitoring begins.

Set the arming delay to zero if constant monitoring is desired, even when the engine is not running.
Non-zero values cause input monitoring after the programmed time has elapsed after engine startup.

4. Threshold 1 and Threshold 2 - These settings are identical to those for Remote Analog Inputs. Refer

to the setup instructions in the paragraphs titled Configuring Remote Analog Inputs on the AEM-2020
to configure these thresholds.

Programmable Outputs

The programmable outputs consist of:

Contact outputs internal to the DGC-2020

o

Programmable contact outputs

o

Run relay, Pre-Start relay, and Start relay outputs

Remote contact outputs on the CEM-2020

Remote analog outputs on the AEM-2020

Configurable elements in the DGC-2020. Configurable elements allow one to take an output from
BESTlogicPlus Programmable Logic and set it up as a pre-alarm or alarm condition, as well as an
input for subsequent logic in the PLC program.

Configuring Contact Outputs on the DGC-2020

Programmable Contact Outputs (See Figure 7-29)
Front Panel Navigation Path: SETTINGS > PROGRAMMABLE OUTPUTS > OUTPUTS

7-26

DGC-2020 Setup

9400200990 Rev X