Basler Electric DGC-2020 User Manual
Page 532

B-100
DGC-2020 Modbus
™ Communication
9400200990 Rev X
Register
Description
Type
Units
Scaling
Factor
R/W
Range
46454
AEM Input 4 Over 2
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
46456
AEM Input 4 Under 1
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
46458
AEM Input 4 Under 2
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
46460
AEM Input 4 Out of
Range Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
46462 -
46498
FUTURE USE
46500
AEM Input 5 Max
Voltage
Int32
DeciVolt
Deci
RW
0 - 100
46502
AEM Input 5 Max
Current
Int32
Milliamp x 10
Deci
RW
40 - 200
46504
AEM Input 5 Min
Voltage
Int32
DeciVolt
Deci
RW
0 - 100
46506
AEM Input 5 Min
Current
Int32
Milliamp x 10
Deci
RW
40 - 200
46508
AEM Input 5 Param Max
Int32
Centi Unit
Centi
RW
(-100000000) – 99999900
46510
AEM Input 5 Param Min
Int32
Centi Unit
Centi
RW
(-100000000) – 99999900
46512
AEM Input 5 Hysteresis
Int32
Deci Percent
Deci
RW
0 – 1000
46514
AEM Input 5 Arming
Delay
Int32
Second
N/A
RW
0 – 300
46516
AEM Input 5 Threshold
1 Activation Delay
Int32
Second
N/A
RW
0 – 300
46518
AEM Input 5 Threshold
2 Activation Delay
Int32
Second
N/A
RW
0 – 300
46520
AEM Input 5 Over 1
Threshold
Int32
Centi Unit
Centi
RW
(-100000000) – 99999900
46522
AEM Input 5Over 2
Threshold
Int32
Centi Unit
Centi
RW
(-100000000) – 99999900
46524
AEM Input 5 Under 1
Threshold
Int32
Centi Unit
Centi
RW
(-100000000) – 99999900
46526
AEM Input 5Under 2
Threshold
Int32
Centi Unit
Centi
RW
(-100000000) – 99999900
46528
AEM Input 5 Over 1
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
46530
AEM Input 5 Over 2
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
46532
AEM Input 5 Under 1
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
46534
AEM Input 5 Under 2
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
46536
AEM Input 5 Out of
Range Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
46538
AEM Input 6 Max
Voltage
Int32
DeciVolt
Deci
RW
0 - 100