A one-line diagram

C

of the breaker hardware configuration can be displayed on the front panel. This

diagram changes in real time to reflect the current state of the configured breakers. The one-line diagram
is disabled by default. See Section 2 for more information.

Specific language modules can be uploaded into the DGC-2020. When the language module upload is
complete, use the Language

D

selector to select the correct language.

When Scrolling Screen is enabled

E

, the front panel summary screen will scroll through the list of Scrolling

Screen Items

F

. The Scrolling Screen Delay

G

determines the scrolling speed. When this feature is disabled

only VOLT, AMP, PH, Hz, OIL, FUEL, TEMP, and BATT are shown on the front panel summary screen.
The phase values are toggled at a rate defined by the Phase Toggle Delay

H

setting. When the phase

toggle delay is set to zero, information for each phase is obtained by pressing the Up or Down arrow keys
on the front panel HMI.

Two custom initializing messages

IJ

are displayed on the initial boot screen of the DGC-2020.

The BESTCOMSPlus Front Panel HMI screen is illustrated in Figure 4-14.

Figure 4-14. Front Panel HMI

A

LCD Contrast Value: Adjustable from 0 to 100 (maximum contrast) in increments of 1.

B

Front Panel Sleep Mode: Enable or Disable.

C

One-Line Diagram: Disable or Enable.

D

Language Selection: Select English, Chinese, Spanish, Russian, French, Portuguese, or German.

E

Scrolling Screen Enable: Enable or Disable.

F

Configurable HMI Summary Settings: Select Scrolling Screen Item 1 through 20.

G

Scrolling Screen Delay: Adjustable from 1 to 120 s in 1 s increments.

H

Phase Toggle Delay: Adjustable from 0 to 120 s in 1 s increments.

I

Initializing Message 1: Accepts an alphanumeric string of up to 16 characters. Displayed on the second

line of the initial boot screen.

J

Initializing Message 2: Accepts an alphanumeric string of up to 16 characters. Displayed on the third

line of the initial boot screen.

Style Number

When a PC operating BESTCOMSPlus is communicating with a DGC-2020, the style number of the
DGC-2020 is automatically displayed on the BESTCOMSPlus Style Number screen.

When configuring DGC-2020 settings off-line, the style number for the unit to be configured can be
entered into BESTCOMSPlus to enable configuration of the required settings.

The BESTCOMSPlus Style Number screen, for hardware version 3, is illustrated in Figure 4-15.

4-14

DGC-2020 BESTCOMSPlus

® Software

9400200990 Rev X