Automatic restart, Exercise timer, Automatic restart -37 – Basler Electric DGC-2020 User Manual
Page 147: Exercise timer -37, Figure 4-29. automatic restart -37, Figure 4-30. exercise timer -37
![background image](https://www.manualsdir.com/files/773941/content/doc147.png)
Automatic Restart
If the DGC-2020 has shut down due to an alarm condition, the automatic restart, when enabled
A
, will
automatically clear alarms. An attempt to restart the engine is made after a predetermined time delay
B
if
the ATS contact input is closed. If an ATS contact is not present, the unit will remain in READY state with
its alarms cleared. A restart will not be attempted if a low fuel alarm or emergency stop is present. The
number of restart attempts
C
is programmable. Automatic restart attempts are recorded in the event log.
The BESTCOMSPlus Automatic Restart screen is illustrated in Figure 4-29.
Figure 4-29. Automatic Restart
A
Auto Restart Enable: Enable or Disable.
B
Auto Restart Interval: Adjustable from 0.5 to 30 min in 0.5 min increments.
C
Auto Restart Attempts: Adjustable from 1 to 10 in increments of 1.
Exercise Timer
The exercise timer is used to start the genset at a predetermined time and run for the user-defined period.
The mode
A
defines how often the genset will run. If monthly is selected, you must select the day of the
month
B
to start. If weekly is selected, you must select the day of the week
C
to start. Settings for Start
Hour
D
and Start Minutes
E
can also be defined. The Run Period Hours
F
and Minutes
G
define how long the
genset will run each time. If Run with Load
H
is enabled, the DGC-2020 will close its GEN breaker during
the RUN time.
Contact inputs and outputs can be assigned to the function. Refer to Section 5, BESTlogicPlus
Programmable Logic, for more information.
The BESTCOMSPlus Exercise Timer screen is illustrated in Figure 4-30.
Figure 4-30. Exercise Timer
A
Mode: Monthly, Weekly, or Daily.
B
Start Day Of Month: Adjustable from 1 to 31 in increments of 1.
C
Start Day Of Week: Sunday, Monday, Tuesday, Wednesday, Thursday, Friday, or Saturday.
D
Start Hour: Adjustable from 0 to 23 in increments of 1.
E
Start Minute: Adjustable from 0 to 59 in increments of 1.
9400200990 Rev X
DGC-2020 BESTCOMSPlus
® Software
4-37