John Deere

The Regeneration Interlock setting

BB

enables John Deere proprietary parameters to be broadcast over the

J1939 CAN bus. This setting is applicable to hardware version 3 units.

The Regeneration Interlock parameter is sent via the Stationary Regeneration/Cleaning CAN Lockout
Message PGN, which is PGN 61194. When the DGC Regeneration Interlock value is set to Enabled, the
DGC-2020 sends a value of 01 (binary) for the two bit “Allowed” configuration which allows regeneration
to occur. When the DGC-2020 Regeneration Interlock value is set to Disabled, the DGC-2020 sends a
value of 00 (binary) for the two bit “Not Allowed” configuration which inhibits regeneration.

The DGC-2020 sends starter engagement requests to the ECU via the SAE J1939 Engine Start Control
PGN. When the DGC-2020 requests the starter to be engaged it sends a value of 01 (binary) for the two
bit starter engagement parameter. Otherwise the DGC-2020 sends a value of 00 (binary) for the two bit
starter engagement parameter.

The BESTCOMSPlus ECU Setup screen is illustrated in Figure 4-20.

Figure 4-20. ECU Setup

A

ECU Type: Standard, Volvo Penta, MTU MDEC, MTU ADEC, MTU ECU7/ECU8, GM/Doosan,

Cummins, MTU Smart Connect, Scania, or John Deere.

B

Generator Parameter Transmit: Enable or Disable.

C

Engine Parameter Transmit: Enable or Disable.

D

Speed Select: Primary or Secondary.

E

Accelerator Position: Adjustable from 0 to 100% in 1% increments.

F

Manual Regeneration: Press to set.

G

Disable Regeneration: Off or On.

H

MDEC Module Type: CAN Module 201, 302, 303, or 304.

I

Speed Demand Switch: Analog CAN, Up Down ECU, Up Down CAN, Analog ECU, Frequency, No CAN

Demand.

J

NMT Alive Transmit Rate: Adjustable from 100 to 500 ms in 100 ms increments.

K

Overspeed Test: Off or On.

L

Governor Param Switch Over: Off or On.

M

Trip Reset: Press to set.

N

Int Oil Prime: Press to set.

O

Speed Up: Press to set.

P

Speed Down: Press to set.

Q

Idle Request: Off or On.

R

Increased Idle: Adjustable from 0 to 1,000 in increments of 1.

S

MTU 50 Hz 60 Hz Switch Setting: Set automatically by the DGC-2020.

T

Engine Start Prime: Off or On.

U

Fan Override: Off or On.