• LSM-2020 (LOAD SHARE MODULE)

General Information

The LSM-2020 is a remote auxiliary device that interfaces to the DGC-2020 and provides analog outputs
to the power system in the form of analog bias signals to the voltage regulator and speed governor. When
the breaker is closed and Load Sharing is enabled, the LSM-2020 will share real power load
proportionally with the other generators on the Analog or Ethernet Load Share Lines.

Refer to Section 7, Setup, for instructions on setting up a DGC-2020 and LSM-2020 for a load sharing
and kW control application.

Features

LSM-2020s have the following features:

A Ramping Function to load and unload generators smoothly

Communications via Ethernet or CAN bus

Demand Start/Stop and Generator Sequencing

kW Load/var Control

kW Load/var Sharing via analog and Ethernet load share lines

Specifications

Operating Power

Nominal ...................................... 12 or 24 Vdc
Range ........................................ 8 to 32 Vdc (Withstands cranking ride-through down to 6 Vdc

for 500 ms.)

Maximum Consumption ............. 4 W
Terminals ................................... P2-3 (–), P2-2 (+), P2-1 (chassis ground)

Analog Inputs

Voltage Configuration ................ 0-10 Vdc

Current Configuration ................ 4-20 mAdc

Terminals ................................... P2-7 (IN+), P2-8 (IN–), P2-9 (V+)

Burden

4 to 20 mAdc .............................. 470

Ω maximum

±10 Vdc ...................................... 9.65k Ω minimum

Analog Outputs

Burden Data ............................... 4-20 mAdc = 500

Ω maximum burden, ±10 Vdc = 667 Ω minimum

burden

Voltage Regulator Bias Output

4-20 mA or

±10 Vdc isolated output signal. (Selectable in increments of 0.1.)

Isolated to 1,500 Vdc between outputs and ground

Terminals ................................... P2-18 (AVR+), P2-17 (AVR–), P2-16 (AVR’)

Governor Bias Output

4-20 mA,

±10 Vdc isolated output signal. (Selectable in increments of 0.1.)

Isolated to 500 Vdc between outputs and ground

Terminals ................................... P2-15 (GOV+), P2-14 (GOV–), P2-13 (GOV’)

9400200990 Rev X

DGC-2020 LSM-2020 (Load Share Module)

9-1

This manual is related to the following products: