beautypg.com

Basler Electric DGC-2020 User Manual

Page 535

background image

9400200990 Rev X

DGC-2020 Modbus

™ Communication

B-103

Register

Description

Type

Units

Scaling

Factor

R/W

Range

46650

AEM Input 8 Out of
Range Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only

46652

AEM Output 1 Max
Voltage

Int32

DeciVolt

Deci

RW

0 – 100

46654

AEM Output 1 Max
Current

Int32

Milliamp x 10

Deci

RW

40 – 200

46656

AEM Output 1 Min
Voltage

Int32

DeciVolt

Deci

RW

0 – 100

46658

AEM Output 1 Min
Current

Int32

Milliamp x 10

Deci

RW

40 – 200

46660

AEM Output 1 Param
Max

Int32

Centi Unit

Centi

RW

(-100000000) – 99999900

46662

AEM Output 1 Param
Min

Int32

Centi Unit

Centi

RW

(-100000000) – 99999900

This manual is related to the following products: