DGC-2020 Modbus
™ Communication
B-103
Register
Description
Type
Units
Scaling
Factor
R/W
Range
46650
AEM Input 8 Out of
Range Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
46652
AEM Output 1 Max
Voltage
Int32
DeciVolt
Deci
RW
0 – 100
46654
AEM Output 1 Max
Current
Int32
Milliamp x 10
Deci
RW
40 – 200
46656
AEM Output 1 Min
Voltage
Int32
DeciVolt
Deci
RW
0 – 100
46658
AEM Output 1 Min
Current
Int32
Milliamp x 10
Deci
RW
40 – 200
46660
AEM Output 1 Param
Max
Int32
Centi Unit
Centi
RW
(-100000000) – 99999900
46662
AEM Output 1 Param
Min
Int32
Centi Unit
Centi
RW
(-100000000) – 99999900
This manual is related to the following products: