Basler Electric DGC-2020 User Manual

Page 531

background image

9400200990 Rev X

DGC-2020 Modbus

™ Communication

B-99

Register

Description

Type

Units

Scaling

Factor

R/W

Range

46400

AEM Input 3 Arming
Delay

Int32

Second

N/A

RW

0 – 300

46402

AEM Input 3 Threshold
1 Activation Delay

Int32

Second

N/A

RW

0 – 300

46404

AEM Input 3 Threshold
2 Activation Delay

Int32

Second

N/A

RW

0 – 300

46406

AEM Input 3 Over 1
Threshold

Int32

Centi Unit

Centi

RW

(-100000000) – 99999900

46408

AEM Input 3Over 2
Threshold

Int32

Centi Unit

Centi

RW

(-100000000) – 99999900

46410

AEM Input 3 Under 1
Threshold

Int32

Centi Unit

Centi

RW

(-100000000) – 99999900

46412

AEM Input 3Under 2
Threshold

Int32

Centi Unit

Centi

RW

(-100000000) – 99999900

46414

AEM Input 3 Over 1
Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only

46416

AEM Input 3 Over 2
Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only

46418

AEM Input 3 Under 1
Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only

46420

AEM Input 3 Under 2
Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only

46422

AEM Input 3 Out of
Range Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only

46424

AEM Input 4 Max
Voltage

Int32

DeciVolt

Deci

RW

0 - 100

46426

AEM Input 4 Max
Current

Int32

Milliamp x 10

Deci

RW

40 - 200

46428

AEM Input 4 Min
Voltage

Int32

DeciVolt

Deci

RW

0 - 100

46430

AEM Input 4 Min
Current

Int32

Milliamp x 10

Deci

RW

40 - 200

46432

AEM Input 4 Param Max

Int32

Centi Unit

Centi

RW

(-100000000) – 99999900

46434

AEM Input 4 Param Min

Int32

Centi Unit

Centi

RW

(-100000000) – 99999900

46436

AEM Input 4 Hysteresis

Int32

Deci Percent

Deci

RW

0 – 1000

46438

AEM Input 4 Arming
Delay

Int32

Second

N/A

RW

0 – 300

46440

AEM Input 4 Threshold
1 Activation Delay

Int32

Second

N/A

RW

0 – 300

46442

AEM Input 4 Threshold
2 Activation Delay

Int32

Second

N/A

RW

0 – 300

46444

AEM Input 4 Over 1
Threshold

Int32

Centi Unit

Centi

RW

(-100000000) – 99999900

46446

AEM Input 4Over 2
Threshold

Int32

Centi Unit

Centi

RW

(-100000000) – 99999900

46448

AEM Input 4 Under 1
Threshold

Int32

Centi Unit

Centi

RW

(-100000000) – 99999900

46450

AEM Input 4Under 2
Threshold

Int32

Centi Unit

Centi

RW

(-100000000) – 99999900

46452

AEM Input 4 Over 1
Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only