Basler Electric DGC-2020 User Manual
Page 311
![background image](https://www.manualsdir.com/files/773941/content/doc311.png)
Figure 7-26. Settings Explorer, Programmable Inputs, Remote Analog Inputs Screen
Configure the following parameters:
1. Label Text - Enter descriptive text that signifies the use of the input. This text appears next to the
threshold status and associated alarm and pre-alarm status in BESTlogicPlus Programmable Logic
and in the event log if any of the input thresholds are configured as an Alarm or Pre-Alarm.
2. Hysteresis (%) - Enter a value for the desired hysteresis for threshold detection. This helps prevent
intermittent detection of thresholds.
3. Input Type - Select Voltage for 0-10 Vdc inputs or Current for 4-20 mA current inputs.
4. Arming Delay - The Arming Delay is the wait time after engine startup, before input monitoring begins.
Set the arming delay to zero if constant monitoring is desired, including while the engine is not
running. Non-zero values direct the input to be monitored after the programmed time has elapsed
after engine startup.
5. Out-of-Range Alarm Type - When the analog input falls outside of its programmed range (as
determined by the Min and Max Input voltage or current settings) an out-of-range indication is
annunciated. If Alarm or Pre-Alarm is selected, annunciation will occur. If Status Only is selected, the
status will be available to BESTlogicPlus Programmable Logic but no annunciation will occur.
6. Parameter Minimum (Param Min) - This setting defines the value that the measured parameter
assumes when the analog input is at its programmed minimum level. If the analog input is below its
programmed minimum level, the measured parameter is limited to this Parameter Minimum setting.
However, the raw analog input value displays the actual voltage or current measured at the analog
input as long as it is within the voltage or current range detected by the input circuit.
7. Parameter Maximum (Param Max) - This setting defines the value that the measured parameter
assumes when the analog input is at its programmed maximum level. If the analog input is above its
programmed maximum level, the measured parameter is limited to this Parameter Maximum setting.
9400200990 Rev X
DGC-2020 Setup
7-23