closed when the phase angle between the two sources is at 0 degrees. This calculation takes into
account the slip rate, generator breaker closing time, and the phase angle difference.
In order to minimize the effects of I/O communications delays on synchronization, it is recommended that
local I/O on the DGC-2020, rather than remote I/O on the CEM-2020, be used for generator breaker open
and close commands, generator breaker status, voltage raise and lower contacts, and speed raise and
lower contacts.
Steps Required to Configure a DGC-2020 Automatic Synchronizer
The following steps describe how to configure the DGC-2020 automatic synchronizer using
BESTCOMSPlus
®:
1. Under the Settings Explorer, click on General Settings and then Style Number. Verify the unit you are
communicating with has the Automatic Synchronizer option present. See Figure 7-39.
Front Panel Navigation Path: SETTINGS > GENERAL SETTINGS > VERSION INFO > DGC-2020 >
STYLE CODE
Figure 7-39. Settings Explorer, General Settings, Style Number Screen
A
DGC-2020 Dial-out modem options for hardware versions 1 and 2.
2. If using a remote module to control the governor or voltage regulator i.e. LSM-2020 or CEM-2020,
click on System Parameters then Remote Module Setup. Enable the applicable module. This step is
not necessary if you are using the DGC-2020’s available contact outputs for AVR and governor
control. See Figure 7-40.
Front Panel Navigation Path: SETTINGS > SYSTEM PARAMS > REMOTE MODULE SETUP
7-36
DGC-2020 Setup